AM-8200
Installation Manual
PAGE - 19
AM8200_manu-inst
Doc. M-162.2-AM8200-ENG Rev A.2
NOTIFIER ITALIA
NOTE:
Connect the 47KΩ , ¼ W EOL
resistor only on last sounder of
the line
ATTENTION
:
Polarity displayed are in Alarm
condition, at idle condition, they
are inverted
General Alarm relay
The main Alarm relay is available in free voltage contacts or as supervised output.
Contact range: max 30 VAC/DC, 2A,
Non-inductive loads.
CNU
COM NO/NC
11 12
Polarized devices (electronic sirens, etc.)
47 K
¼ W
12
11
Non-polarized devices (Bells, relays, etc.)
47 K
¼ W
2 x 1N 4004
12
11
Main Alarm output
Supervised output (resettable fuse 0.3A) with EOL resistor 47K
Ω
Setting of the general
Alarm output with N.O.
contact (Jumper JALL).
Setting of the general
Alarm output with N.O.
contact (Jumper JALL).
Setting of the general
Alarm output as
supervised output
(Jumper JALL).