AM-8200
Installation Manual
PAGE - 23
AM8200_manu-inst
Doc. M-162.2-AM8200-ENG Rev A.2
NOTIFIER ITALIA
LIB-8200 (Expansion Board )
CNU
terminal block
Address DIP SWITCH SW1 on LIB-8200 Board
Dip switch
Note
1
2
3
4
OFF
ON
OFF
OFF
if the board is mounted on AM-8200
is necessary to set the address n° 2
OFF
OFF
ON
OFF
if the board is mounted on AM-8200-BB
is necessary to set the address n° 4
Detection Lines connection on AM-8200
N°
Description
Characteristics
Note
8
Line 2 B-
Detection LINE 4 (
if the board is mounted on AM-8200 )
Detection LINE 8 (
if the board is mounted on AM-8200-BB )
7
Line 2 B+
6
Line 2 A-
5
Line 2 A+
4
Line 1 B-
Detection LINE 3 ( if the board is mounted
on AM-8200
)
Detection LINE 7 ( if the board is mounted
on AM-8200-BB
)
3
Line 1 B+
2
Line 1 A-
1
Line 1 A+
Dip-switch
LIB Address
TX-RX Line 3
TX-RX Line 4
Alarm Led
Led Fault
User terminal block
Connector for interconnections with
AM-82-MB
/
AM-82-BBMB