PAGE - 32
INSTALLATION MANUAL
AM-8200
NOTIFIER ITALIA
Doc. M-162.2-AM8200-ENG Rev A.2
AM8200_manu-inst
Network with AM82-BST-C board installed on HLSPS25 EN 54.4 PSU
N.B. :
On the CAN-BUS network, it’s possible to install max. 8 of AM82-BST-C cards
CanBus Netwok Cable
CBUS 218AWG:
CAN‐BUS Cable 2x18 AWG 18 Fire Resistant PH60 EN 50200 Color Blue
Core Type :Flexible CI. 5‐Tinned Copper
Total shield: Aluminum /Polyester tape 25/23 µm .
Drain : Tinned copper 7x0,20
Can Bus Typology
Similar to all RS-485 communication line, the CAN Bus is a Point-to-Point sequential connection.
The wire must have a 120 Ohm resistor at each end (on board on all boards)
The typology used is a Class A (closed Loop)
.
Note that it’s not necessary to follow the sequential series on the peripherals addresses.
T-taps are not permitted.
Cable must be wired in conduits separated by the mains power line and anyway wiring must be compliant to laws
and rules valid in the country of the installation.
500 m Node-Node
500 m Node-Node
500 m Node-Node
500 m Node-Node
500 m Node-Node
500 m Node-Node