5. C300 Configuration Form Reference
5.4. IOLINK Block
144
Series 8 C300 Controller User's Guide
Honeywell
R500
April 2017
Plain Text
Parameter Name
User
Configurable
Notes
Channel B Errors
PRIIFCHNERRB
No
The number of I/O link
channel B errors
encountered locally by
the primary link
interface.
Channel B Silences
PRIIFCHNSILB
No
The number of I/O link
silences on channel B
encountered locally by
the primary link
interface.
Channel B- Edges
PRIIFCHNMNB
No
The number of I/O link
channel B missed
minus edge transitions
encountered locally by
the primary link
interface.
Channel B+ Edges
PRIIFCHNPLB
No
The number of I/O link
channel B missed plus
edge transitions
encountered locally by
the primary link
interface.
Last Error
PRIIFCOMMERR
No
The last I/O link
communications error
experienced by the
primary link interface.
Processor Status
PRIIFSTS
No
The status of the link
processor for the
primary link interface.
Last IOL Command
LASTIOLCMD
No
The last I/O link
command requested
through the COMMAND
parameter or the last
SELECT_CH_A /
SELECT_CH_B
command automatically
issued when periodic
channel swap is
enabled.
Содержание Experion C300
Страница 8: ......
Страница 18: ......
Страница 30: ......
Страница 34: ......
Страница 45: ......
Страница 90: ......
Страница 107: ......
Страница 164: ......
Страница 199: ......
Страница 221: ......
Страница 236: ......
Страница 242: ......
Страница 285: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...