Series 8 C300 Controller User's Guide
Honeywell
195
7. C300 Controller Operation
7.8. Disable Synchronization command
7.8
Disable Synchronization command
To disable synchronization manually to a redundant C300 Controller pair, perform the
following steps.
Prerequisites
You can view active redundant C300 Controller pair on the
Monitoring
tab in
Control Builder.
The primary and secondary C300 Controllers are synchronizing, synchronized or in
standby state.
To Disable Synchronization, perform the following steps.
Step
Action
1
In the
Monitoring
tab, double-click the primary
C300
icon. The
Parameters
configuration form.
2
Click the
Redundancy
tab.
3
Click
Disable Synchronization
.
4
Click
Yes
button to confirm the action and issue the Disable Synchronization
command.
5
Confirm that the
Auto Synchronization State
becomes
DISABLED
.
6
Click
OK
to close the
Parameters
form.
7
This completes the procedure.