Series 8 C300 Controller User's Guide
Honeywell
193
7. C300 Controller Operation
7.6. Initiating C300 Controller Shutdown
ATTENTION
Shutting down the C300 Controller interrupts the transfer of data to the
Experion LX system. Be sure your system can tolerate the loss of live data,
while the C300 Controller is in its RDY state.
1. Project Tree
Gray
N/A
2. Loaded, not monitoring
Gray
N/A
3. Communication Failure
Red
N/A
4. InActive
Blue
CEESTATE = IDLE
5. Active
Green
CEESTATE = RUN
6. Configuration Error
Red
CEESTATE = FAIL, NOT_LOADED
7.6
Initiating C300 Controller Shutdown
To initiate a shutdown command to the C300 Controller, which results in the C300
Controller rebooting to its RDY state or boot firmware, perform the following steps.
Step
Action
1
Using Control Builder, select the
Monitoring
tab.
Double-click the C300 Controller icon to open the
C300 Block
configuration
form.
2
On the
Main
tab, click
Controller Command
box and select
Shutdown
from
the list.
3
Click
Yes
to confirm the action.
4
Wait for the C300 Controller to reboot to its RDY state.
5
This completes the procedure.