3. C300 Controller Installation and Upgrades
3.2. C300 Controller installation
R500
April 2017
Series 8 C300 Controller User's Guide
Honeywell
39
Step
Action
4
Be sure component side of IOTA is facing up. Refer to the figure below.
Assemble mounting screws, washers and spacers provided. Insert spacers
and washers between backside of IOTA and front of channel.
5
Position the assembled IOTA board at the proper mounting location.
6
Thread the four mounting screws only
half-way
to attach the IOTA board to
the panel. Do
not
tighten.
7
Tighten the mounting screws securing the IOTA board to the channel.
8
Connect FTE-A and FTE-B Ethernet link cables to the RJ-45 connectors on
C300 IOTA board.
The
Yellow
Cat5 cable connects to the "
FTEA
" connector on the IOTA.
The
Green
Cat5 cable connects to the "
FTEB
" connector on the IOTA.
9
Connect the Orange Redundancy cable to the
REDUNDANCY
connector on
the secondary controller IOTA.
Route the cable to the primary controller location and connect it to the
REDUNDANCY connector on the primary controller IOTA.