System Time tab
The System Time tab contains information about the C300 Controller's time source and
synchronization with that time source. The "System Time" and "System Time
Synchronization Status" subgroups on this tab provide current controller system time and
indicates the time source with which it is synchronized and status of synchronization with
that source. "SNTP Status" and "GPS Status" subgroups provide meaningful statistics
related to time synchronization with SNTP Servers and GPS sources, along with their
status. The following table summarizes the parameter data you can monitor on the
System Time
tab of the configuration form for the selected C300 block.
Plain Text
Parameter Name
User
Configurable
Notes
System Time
Current System Time
CURTIME
No
Shows current system
time.
Current System Time
Source
TIMESOURCE
No
Shows source of system
time. Default is Simple
Network Time Protocol
(SNTP).
System Time Synchronization Status
Time Synchronization
Status
TIMESYNCSTAT
No
Shows time sync status.
Time of Last Time
Sync
TIMELASTSYNC
No
Shows time controller time
synced with time source
Skew at Last Time
Sync (msec)
TIMELASTSKEW
No
Shows time skew from last
synced time.
SNTP Status
SNTP Server
Address
SNTPADDRESS
No
Shows FTE address of
SNTP Server.
SNTP Status
SNTPSTAT
No
Shows status for SNTP
time source.
SNTP Skew Limit
(msec)
SNTPSKEWTHLD
No
Shows the limit set for the
skew between the
controller time and the
SNTP time source
Содержание Experion C300
Страница 8: ......
Страница 18: ......
Страница 30: ......
Страница 34: ......
Страница 45: ......
Страница 90: ......
Страница 107: ......
Страница 164: ......
Страница 199: ......
Страница 221: ......
Страница 236: ......
Страница 242: ......
Страница 285: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...