5. C300 Configuration Form Reference
5.4. IOLINK Block
146
Series 8 C300 Controller User's Guide
Honeywell
R500
April 2017
Plain Text
Parameter Name
User
Configurable
Notes
Channel B- Edges
SECIFCHNMNB
No
The number of I/O link
channel B missed
minus edge transitions
encountered by the
secondary link
interface.
Channel B+ Edges
SECIFCHNPLB
No
The number of I/O link
channel B missed and
the edge transitions
encountered by the
secondary link
interface.
Last Error
SECIFCOMMERR
No
The last I/O link
communications error
experienced by the
secondary link
interface.
Active Supervisor Information
Periodic Swap
Enabled
PERSWAPENB
No
Indicates if the periodic
cable swap diagnostic
is enabled or disabled.
Channel A Total
Errors
TOTCHNERRA
No
The total I/O Link Errors
on channel A.
Channel A Total
Silences
TOTCHNSILA
No
The total I/O Link
silences on channel A.
Channel A- Total
Edges
TOTCHNMNA
No
The total I/O Link
missed minus edge
transitions on channel
A.
Channel A+ Total
Edges
TOTCHNPLA
No
The total I/O Link
missed and the edge
transitions on channel
A.
Channel B Total
Errors
TOTCHNERRB
No
The total I/O Link errors
on channel B.
Содержание Experion C300
Страница 8: ......
Страница 18: ......
Страница 30: ......
Страница 34: ......
Страница 45: ......
Страница 90: ......
Страница 107: ......
Страница 164: ......
Страница 199: ......
Страница 221: ......
Страница 236: ......
Страница 242: ......
Страница 285: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...