Series 8 C300 Controller User's Guide
Honeywell
49
4. C300 Controller Configuration
4.2. Create C300 Controller and CEE function blocks
Step
Action
Result
8
In the Temperature High Alarm (degC)
field, accept the default or enter a value
at which an alarm is generated for
controller hardware high temperature.
Press <Tab>.
Note setting this value at 0 disables the
temperature high alarm.
Moves cursor to the
CPU Free Low
Alarm (%)
field.
9
Accept the default or enter the desired
value. Press <Tab>.
Note
: Do not set lower than the default
value of 20%.
Moves cursor
to Simulation Node
Configuration
section.
10
If this block is to be loaded to a
simulation environment, select the Load
to simulation Environment check box.
Press <Tab>.
Moves cursor to
Host IP Address
field
11
If the controller is to be a SIMC300
controller you must enter the IP Address
of the SIMC300 controller. Press <Tab>.
Moves the Cursor moves to the
Host
Name
field.
12
Enter the host name of the SIMC300
controller if it does not appear in the field.
13
Click
Server History
tab.
The Server History configuration form
appears.