Series 8 C300 Controller User's Guide
Honeywell
R500
April 2017
7. C300 Controller Operation
7.4. Control Builder block icon descriptions
Icon
Represents . . .
C300 Controller
(C300STATE)
(red)
C300 is non-redundant and not communicating.
No Communication
(Offnet)
(red, simulation)
C300 is non-redundant. Simulation mode
enabled.
No Communication
(Offnet)
(red & white)
Primary C300 is not communicating.
No Communication
(Offnet)
(white & red)
Secondary C300 is not communicating.
No Communication
(Offnet)
(yellow)
C300 is non-redundant.
No Database
(yellow,
simulation)
C300 is non-redundant. Simulation mode
enabled.
No Database
(yellow & yellow)
Primary C300 is not synchronized and partner
C300 is visible
No Database
(yellow &
shadow)
Primary C300 is not synchronized and partner
C300 is absent or incompatible
No Database
(blue)
C300 is non-redundant.
Idle
(blue,
simulation)
C300 is non-redundant. Simulation mode
enabled.
Idle
(blue & white)
Primary C300 is synchronized.
Idle
(blue & white,
pause)
Primary C300, standby synchronization.
Idle
(blue & yellow)
Primary C300 is not synchronized and partner
C300 is visible.
Idle
(blue & shadow)
Primary C300 is not synchronized and partner
C300 is absent or incompatible.
Idle
(green)
C300 is non-redundant.
Run or OK
Содержание Experion C300
Страница 8: ......
Страница 18: ......
Страница 30: ......
Страница 34: ......
Страница 45: ......
Страница 90: ......
Страница 107: ......
Страница 164: ......
Страница 199: ......
Страница 221: ......
Страница 236: ......
Страница 242: ......
Страница 285: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...