![Honeywell ADEMCO Vista-12C Скачать руководство пользователя страница 98](http://html.mh-extra.com/html/honeywell/ademco-vista-12c/ademco-vista-12c_installation-and-setup-manual_153257098.webp)
Installation and Setup Guide
7-2
hours 55 minutes of Test mode), the keypad emits a double-beep every 30 seconds to alert
that the end of
Test mode is nearing.
Checking Zones Using One-Man Walk Test (Sniffer Mode)
Use this mode to test all zones (wired and wireless) that have been programmed. Make sure
all partitions are disarmed before trying to enter this mode, since this is a system-wide
command.
1. Press [Installer code] + [#] + 3.
NOTE:
If the communicator is in the process of sending a report to the central station,
the system will not go into the Sniffer mode. If so, wait a few minutes, and try
again.
The keypads in all partitions will display all zone numbers (in all partitions)
programmed in the system. Fault each zone in turn, causing each one to send a signal.
As the system receives a signal from each of the zones, the corresponding zone number
disappears from the display.
2. After all zones have been checked, exit the Sniffer Mode by keying [Installer code] +
OFF.
IMPORTANT:
Sniffer mode does not automatically expire. You must manually exit Sniffer
Mode (by entering [Installer code] + OFF) to return to normal operation.
NOTES:
• All BR type RF units (e.g., 5804) must physically be activated to clear the display.
• When
one
button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other
buttons on that transmitter are cleared. This also applies to multiple-loop transmitters
(e.g., 5816 and 5817).
• Any transmitter not “enrolled” or any zone that is not faulted will not turn off its zone
number.
Go/No Go Test Mode
The Go/No Go Test verifies adequate RF signal strength from the proposed transmitter
location, and allows you to reorient or relocate transmitters if necessary, before mounting the
transmitters permanently. This mode is similar to the Transmitter Test mode, except that
the wireless receiver gain is reduced. This will enable you to make sure that the RF signal
from each transmitter is received with sufficient signal power when the system is in the
normal operating mode.
1. Enter [Installer code] + [#] + 4 from the partition being tested. Repeat this test for each
partition.
2. After you have placed transmitters in their desired locations and the approximate length of
wire to be run to sensors is connected to the transmitter's screw terminals (if used), fault
each transmitter. Do not conduct this test with your hand wrapped around the transmitter.
a. Keypad beeps three times to indicate signal reception and displays the appropriate zone
number.
b. If the keypad does not beep, you should reorient or move the transmitter to another
location. Usually a few centimeters in either direction is all that is required.