Installation and Setup Guide
4-18
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*186
Display Options
Entry 1: Latch first alarm in the display
0 = disable; 1 = enable
Entry 2: Blank the display (except for AC
loss) when not in exit delay, or 30
seconds after disarm
0 = disable; 1 = enable
Select the desired keypad display options.
Entry 1: If enabled, only the first zone that went into
alarm is displayed. Pressing the READY key will scroll
once through the other zones that went into alarm,
then the first zone in alarm will again be displayed.
NOTE:
Must be “11” for
EN50131-1/prEN50131
-3
compliance
*187
Sounder Mimic on Trigger 1
0 = no sound output on trigger 1
1 = mimic keypad 1, address 16
2 = mimic keypad 2, address 17
3 = mimic keypad 3, address 18
4 = mimic keypad 4, address 19
5 = mimic keypad 5, address 20
6 = mimic keypad 6, address 21
7 = mimic keypad 7, address 22
8 = mimic keypad 8, address 23
Enable this option if you want an external device
connected to trigger 1 to mimic keypad sounding.
NOTE:
If using this option, trigger 1 must be
dedicated to only this function; do not assign any other
functions to trigger 1.
*188
Keypad Sabotage Options
Entry 1: Keypad Lockout:
0 = disable; 1 = enable 15 minute lockout
Entry 2: Keypad Supervision and Tamper
Fault Detection: 0 = no, 1 = yes
Entry 1. If selected, will lockout the keypad for 15
minutes if 30 keystroke entries (6 attempts of code +
command) are made without a valid user code being
detected. While the keypad is locked out, a message
"Code Sabotage" will be displayed on the keypads in
the partition that is locked out. A message will be
transmitted to the central station (461 Wrong Code
Entry), as well as being logged in the event log.
Entry 2. Enables or disables keypad supervision (ECP
addresses 16-23) in the control. If selected, keypads are
supervised for connection and tamper. These
conditions cause a trouble when disarmed, alarm when
armed.
NOTE:
Must be “11” for
EN50131-1/prEN50131-3
compliance
AUI Enable
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*189
AUI Enable
0 = disabled
1 = partition 1
2 = partition 2
3 = common partition
Enter each AUI’s home partition.
AUI 1 address must be set to 1.
AUI 2 address must be set to 2.
NOTE:
Use of an AUI does not affect the number of
standard keypads supported.