Menu Mode Programming
5-3
PROMPT
VALID ENTRIES
EXPLANATION
17 Zone Type
Perimeter 03
Zone Type (ZT)
00-24, 77, 82, 90-93 = zone
type (see table at right)
Each zone must be assigned to a zone type, which
defines the way in which the system responds to
faults in that zone.
Enter the Zone Type code from the list below:
Note:
If 00 is entered,
Delete Zone ?
will be
displayed.
00 = Not used
14 = Gas
01 = Entry/exit #1
16 = Fire w/Verify
02 = Entry/exit #2
20 = Arm–STAY*
03 = Perimeter
21=Arm–AWAY*
04 = Interior Follower
22=Disarm*
05 = Trouble Day/Alarm
Night
23=No Alarm Resp
06 = 24-Hr Silent
24=Silent Burglary
07 = 24-Hr Audible
77 = Keyswitch
08 = 24-Hr Aux
81 = AAV Monitor Zone
09 = Fire
82 = Blockschloss
10 = Interior w/Delay
90-93 = Configurable
12 = Monitor Zone
*5800 button-type transmitters only
17 Partition
1
Partition No. (P)
1-3 = partition
[
∗
] to continue
Enter the Partition number for this zone.
Partition 1 is shown entered. (3 = Common
Partition).
17 Report Code
1st 01 2nd 00 10
Report Code (RC)
First Digit: 01-09, 10 for 0, 11
for B, 12 for C, 13 for
D, 14 for E, 15 for F
00 to disable
Second Digit: same as above
[
∗
] to continue
Enter the report code for this zone, which consists of 2
hexadecimal digits, each in turn consisting of 2
numerical digits. For example, for a report code of
“10,” enter 01 and 00.
For Contact ID
®
, entering any non-zero entry as the
first digit enables the report code for this zone. Refer
to the
System Communication
section for
information about report codes and formats.
17 HARDWIRE TYPE
EOL 0
Basic Wired Type
0 = EOL; 1 = NC; 2 = NO
3 = zone doubling (ZB)
4 = double-balanced (DB)
[
∗
] to continue
This prompt appears only for zone numbers 02-06.
Zone 1 is automatically set for EOL operation.
02 Response Time
1
Response Time (RT)
0 = 10mSec
2 = 700mSec
1 = 400mSec 3 = 1.2 seconds
[
∗
] to continue
This prompt appears only for basic wired zones 01-
06 (zone 02 is used as an example in display).
NOTE:
If zone doubling is being used, the
response time set for zones 02-06 automatically
applies to each zone’s associated doubled zone.