Installation and Setup Guide
2-4
Wiring Run Chart For Devices* Drawing Aux Power From The Control (12V+ & 12V–)
Wire
TOTAL CURRENT DRAIN OF ALL DEVICES CONNECTED TO A SINGLE WIRE RUN
Size
50 mA or less
100 mA
300 mA
500 mA
600 mA
0.6mm O.D.
152m
76m
24m
15m
13m
0.8mm O.D.
228.6m
116m
40m
24m
20m
1mm O.D.
396m
198m
67m
40m
35m
1.2mm O.D.
457m
305m
100m
70m
52m
* Includes Keypads, RF Receivers, Zone Expander/Relay Units, or TeleCommand Phone Module.
Maximum wire lengths for any device that is wired directly to the control can also be determined from the Wiring Run
Chart, based on the current drain of that device alone.
The length of all wire runs for all partitions combined must not exceed 457m when unshielded quad conductor cable is
used (228m if shielded/screened cable is used). This restriction is due to the capacitive effect on the data lines when
quad cable is used.
Sounder (Siren) Connections
1. Make sounder connections to alarm output terminals 3
(+) and 4 (–).
For supervised output, continue with steps 2 and 3.
2. Cut the red Siren Supervision Jumper located above
terminals 2 and 3 on the control board.
3. Connect a 2k ohm resistor across the terminals of the
last sounder.
+
+
_
_
2
EXTERNAL ALARM
SOUNDER
TERMINALS ON
CONTROL BOARD
ALARM
OUTPUT
TERMINALS
V48sounder-001-V0
3
4
CUT RED JUMPER ON CONTROL
BOARD TO ENABLE SIREN
(SOUNDER) SUPERVISION.
2000
OHM
EOL
RESISTOR
IF SIREN SUPERVISION IS ENABLED
(RED JUMPER ON CONTROL BOARD IS CUT)
CONNECT A 2000 OHM RESISTOR ACROSS
THE EXTERNAL SOUNDER AS SHOWN BY
THE DOTTED LINE.
DO NOT CONNECT THE RESISTOR AT THE
ALARM OUTPUT TERMINALS THEMSELVES!
OBSERVE
POLARITY
Figure 4. Sounder Wiring (Supervised)
Notes
•
The 12VDC sounder output activates
when an alarm occurs.
•
Total current drain from this output
cannot exceed 2 amps (going beyond 2
amps will overload the power supply,
or may cause the electronic circuit
protecting the sounder output to
activate).
•
You must install a battery, since the
battery supplies this current.
•
Do NOT perform steps 2 and 3 if using
a self-activated siren.