VISTA-120 Installation and Setup Guide
5-4
*32
Primary Subscriber’s Account
Number (partition-specific)
Enter
00-09; B-F (11-15)
Enter a 3- or 4-digit (depending on report format) primary subscriber account
number. Each number requires a 2-digit entry so as to allow entry of
hexadecimal digits (B-F). If a 3-digit account number is to be used, enter data
only in the first 3 locations, and enter * in the fourth location.
*33
Primary Phone Number
Enter
0-9; #11
for *
, #12
for
#, #13
for
a 2-
second pause.
Enter the primary central station phone number, up to 17 digits. This is the
phone number the control will use to transmit Alarm and status messages to
the central station. Do not fill unused spaces.
NOTE:
Backup reporting is automatic only if a secondary phone number is
entered.
*34
Secondary Phone Number
Enter
0-9; #11
for *
, #12
for
#, #13
for
a 2-
second pause.
Enter the secondary phone number, up to 17 digits. The secondary phone
number
is used if communication on the primary number is unsuccessful, or if
split/dual reporting is desired. Do not fill unused spaces.
NOTE:
If this field is programmed, a secondary subscriber account number
(field *90)
must also be programmed.
*35
Download Phone Number
Enter
0-9; #11
for *
, #12
for
#, #13
for
a 2-
second pause.
Enter the downloading phone number, up to 17 digits. Do not fill unused
spaces.
NOTE:
This field is applicable only if downloading is utilised.
*36
Download ID Number
Make entries as 2-digit numbers as follows:
00=0 01=1 02=2 03=3 04=4 05=5
06=6 07=7 08=8 09=9 10=A 11=B
12=C 13=D 14=E 15=F
Enter eight digits.
NOTE:
This field is applicable only if downloading is utilised.
*37
Download Command Enables
0
= disable
1
= enable
Enabling a function means that you are able to perform that function via the
ADEMCO Compass Downloading software.
Functions are as follows: Dialler Shutdown; System Shutdown; Restrict
Access*; Remote Bypass; Remote Disarm; Remote Arm; Upload Program;
Download Program.
*Restrict download access when the system is armed: can only arm unarmed
partitions, upload program/event log, command relays and request status.
*38
Prevent Zone XXX Bypass (partition-
specific)
Enter a zone number
(001-128)
.
Enter
000
if all zones can be bypassed.
Enter three digits for zone that cannot be bypassed by the user.
This selection does not affect fire zones, which the system prevents from
being bypassed.
*39
Enable Open/Close Report for
Installer Code (partition-specific)
0
= disable
1
= enable
If enabled, whenever the Installer Code is used to arm or disarm the partition,
an open/close report is sent to the central station.
*40
Enable Open/Close Report for
Keyswitch
0
= disable
1
= enable
If enabled, whenever the keyswitch is used to arm or disarm the partition, an
open/close report is sent to the central station.
*41
Normally Closed or EOLR (Zones 2-
8)
0
= EOLR used
1
= normally closed
If
0
, end-of-line resistors must be used on zones 2-8.
If
1
end-of-line resistors cannot be used and only
normally closed
devices
must be used.
*42
Suppress Fire Relay
0
= disable
1
= enable
If enabled, the system does not activate 4204/Powerline Carrier Device for fire
alarms.
FIELD
TITLE and DATA ENTRIES
EXPLANATION
Содержание ADEMCO VISTA-120
Страница 2: ...ii ...
Страница 18: ...VISTA 120 Installation and Setup Guide 2 8 ...
Страница 70: ...VISTA 120 Installation and Setup Guide 5 16 ...
Страница 88: ...VISTA 120 Installation and Setup Guide 7 4 ...
Страница 90: ...VISTA 120 Installation and Setup Guide 8 2 ...
Страница 100: ...VISTA 120 Installation and Setup Guide A 2 ...
Страница 104: ......
Страница 106: ......
Страница 113: ......