Chapter 8 High-speed Link
8
Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User
’s Guide R220
Honeywell
January 2019
8) Setting of High-speed link block
Double-click the applicable index number of Configuration file uploaded and designates the
‘Read
area
’ and ‘Save area’.
[Figure 8.4.5] Setting of High-speed link block
Classification
Details
Master
Station No.
Display the Master station no.
Station No. *1
Setting range for the slave : 0 ~ 126
If identical station No. is set, communication will not be normal.
Mode *1
Send: Transmission the data from master module to slave module.
Receive : Transmission the data from slave module to master module.
Read area
(Master module
→
Slave module)
2MLK
Area to set the start address of device used for Sending.
Setting device : P, M, K, F, T, C, U, Z, L, N, D, R, ZR
2MLI
Area to set the start address of device used for Sending.
Setting device : A, M, I, Q, R, W, F, K, L, N, U
Save area
(Slave module
→
Master module)
2MLK
Area to set the start address of device used for Receiving.
Setting device : P, M, K, F, T, C, U, Z, L, N, D, R, ZR
2MLI
Area to set the start address of device used for Receiving.
Setting device : A, M, I, Q, R, W, F, K, L, N, U
Sending data
Receiving data
(Byte)
Display input/output points of slave module by the bytes.
- In case of I/O module of 8 bits or less, please set 1 byte.
*1 : Area is not able to set
[Table 8.4,3] Setting of High-speed link block