Chapter 10 Program Example
5
Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User
’s Guide
R220
Honeywell
January 2019
The following is setting method about MPL-BSSA.
1) Insert Slave -> select MPL ->
click “Add” ->set “Station address” as 6
[Figure 10.1.8] Insert Slave
2) Slave Configuration -> Configure based on module equipped in the MPL-BSSA.
[Figure 10.1.9] Slave Configuration
Slot
Module
Type
I Len.
O Len.
Contents
1
Digital Output
QB
-
4
Digital Output 4 byte (MLE-TN32A)
2
Digital Input
IB
4
-
Digital Input 4 byte (MLE-DC32A)
3
Analog Input
IB
8
-
Analog Input 8 byte (MLF-AD04A)
4
Analog Output
QB
-
8
Analog Output 8 byte (MLF-DV04A)
5
Analog Output
QB
-
8
Analog Output 8 byte (MLF-DC04A)
6
Analog Input
IB
8
-
Analog Input 8 byte (MLF-RD04A)
7
Digital Output
QB
-
2
Digital Output 2 byte (MLE-RY16A)