HLP-C100 Series
HLP-C100 Series Operating Manual
-
83
-
Transmit data
Field
Description
01
FC address
05
Function
00 40
0x0040 convert to decimal number is 64. The register address 64
is parameter write control
FF 00
0000-Parameter changes are written to the RAM;
FF00- Parameter changes are written to the RAM and
EEPROM;
8D EE
CRC check
Transmit data
Field
Description
01
FC address
05
Function
00 40
0x0040 convert to decimal number is 64. The register address 64
is parameter write control
FF 00
0000-Parameter changes are written to the RAM;
FF00- Parameter changes are written to the RAM and
EEPROM;
8D EE
CRC check
12.5 Preset Single Register
Example: set C01.01 = 1
Transmit: 01 06 03 F1 00 01 19 BD (Hexadecimal)
Receive: 01 06 03 F1 00 01 19 BD (Hexadecimal)
Transmit data
Field
Description
01
FC address
06
Function
03 F1
The register address of C01.01 is 101*10-1=1009 (0x03F1)
00 01
The parameter value is 1
19 BD
CRC check