Function: Def ine the minmum delay time f rom receiving a request to
transmitting the respond out.
C08.35 Function Description
Range
Unit
Default Setting
Min. Response Delay
0.001~0.50
s
0.010
Option: [0] No f unction Control word timeout is not reset;
[1] Do reset Control word timeout is reset;
Function: Resetting control word timeout will remove any timeout f unction;
C08.06 Function Description
Range Unit Default Setting
Reset Control Word Time Out
0~1
0
Function: Select the address for the bus.
C08.31
Function Description
Range
Unit
Default Setting
Address
0~247
1
Option: [0] 2400;
[1] 4800;
[2] 9600;
[3] 19200;
[4] 38400;
Function: Select baud rate for Port.
C08.32 Function Description
Range
Unit
Default Setting
Port Baud Rate
0~9
bit/s
2
Option: [0] Even parity (1 stop bit);
[1] Odd parity (1 stop bit) ;
[2] No parity (1 stop bit) ;
[3] No parity (2 stop bit) ;
C08.33 Function Description
Range
Unit
Default Setting
Port Parity
0~3
2
C08.3* FC Port Setting