HLP-C100 Series
HLP-C100 Series Operating Manual
-
79
-
Chapter 12 Communication protocol
HLP-C100 series inverter follows the standard Modbus RTU protocol.
12.1 Format speci
fi
cation
12.2 Coil addressing
Address
Function code
Data
CRC
8 bits
8 bits
N*8 bits
16 bits
1) Address: 1-247
2) Function: HLP-C100 support following f unction code
01: Read Coil Status
03: Read Holding Registers
05: Force Single Coil
06: Preset Single Register
15: Force Multiple Coils
16: Preset Multiple Regs
3) DATA: N×8bits
4) CRC: CRC check
Coil address
R/W
Description
0-15
R, W
Frequency converter control word (see
following table)
16-31
R, W
Frequency converter speed or setpoint
32-47
R
Frequency converter status word(see
following table)
48-63
R
Frequency converter output f requency
64
W
Parameter write control
0000-Parameter changes are written to the
RAM;
FF00- Parameter changes are written to the
RAM and EEPROM;
65-65535
Reserved