Chapter 8 Accessory Speci
fi
cation
8.1 Braking Resistor
8.2 LCP Mounting Kit
When the motor acts as a generator, the braking resistor consumes surplus
energy resulting f rom motor braking to achieve fast stop. And to prevent the
intermediate circuit voltage is too high to trip eventually.
Note: The braking resistor will be very hot, and will have a risk of
fi
re, if the
transistor in the braking unit is damaged and shorted. The installation
length of the braking resistor should be not less than 5 meters.
Brake resistor (option):
Model
Braking Resistor Speci
fi
cation
Suitable
Motor(KW)
Ω
KW
HLP-C1000D3721
310
0.25
0.37
HLP- C1000D7521
145
0.065
0.75
HLP- C10001D521
65
0.25
1.5
HLP- C1000D3723
310
0.25
0.37
HLP- C1000D7523
145
0.065
0.75
HLP- C10001D523
65
0.25
1.5
HLP- C1000D7543
620
0.065
0.75
HLP- C10001D543
310
0.25
1.5
HLP- C10002D243
210
0.285
2.2
Note: An external braking unit is needed when connecting braking resistor for
the FC which power is less than 220V/380V 0.75kW(included) .
External LCP Communication Cable is network cable. Length should
not exceed 15m. More than
fi
ve types of shielded cable is recommended for use
in the presence of electromagnetic interference environment.
An external LCP mounting kit is provided; users need to open a hole (size
as shown below). The installation steps are as follows:
8.2.1 External LCP Communication Cable
8.2.2 Mounting steps