HLP-C100 Series
HLP-C100 Series Operating Manual
-
35
-
7.2 Parameter Group 01: Load and Motor
*C01.00 Function Description
Range
Unit
Default Setting
Con
fi
guration Mode
0~3
0
Option: [0] Speed open loop, for general applications;
[3] Process closed loop, feedback signal is a process unit, such as:
pressure
、
temperature etc. When process closed loop is selected, the
motor can only run clockwise. For detailed parameter settings, please
refer to C07.3*.
Attention: If con
fi
guration mode is changed, C03.03 will be restored to factory
setting.
C01.0* General Settings
*C01.20 Function Description
Range
Unit Default Setting
Motor Power
Dep. Motor date KW
*
Function: Select the KW value that corresponds to the rated power of the
motor.
Description of choice: Factory settings depend on the inverter size, there is one
or two undersize or one oversize in comparison with factory setting.
Attention: Changing the value of this parameter af fects the setting of
C01.22-C01.25.
*C01.22 Function Description
Range
Unit
Default Setting
Motor Voltage
50~1000
V
*
Function: Select a value that equals the nameplate data on the motor.
Description of choice: Default setting depends on the inverter size.
*C01.23 Function Description
Range
Unit
Default Setting
Motor Frequency
20~400
Hz
*
Function: Enter the rated motor f requency f rom the nameplate data.
Description of the choice: Default setting depends on the inverter size.
Attention: Changing this parameter affects motor nominal speed set in C01.25.
C01.2* Motor Date
Attention: Data of Parameter group C01.2* can not be changed when motor is
running.