HCA Series Installation Manual
Page 27 of 58
V2.15
CHARGER FAULT
This screen is displayed when the battery charger is not operating
properly.
AC FAULT
This screen is displayed when there is no AC power or the AC power is
low.
GROUND FAULT
This screen is displayed when there is an earth ground fault between at
least one control panel circuit and earth ground.
Remote Panel err
This screen is displayed when there is a problem communicating to the
remote annunciator and the panel has been configured with the remote
annunciator.
Account # Trbl
This screen is displayed if the DACT fails to communicate to the central
station. The account that failed will be indicated by a number, 1
– 4.
Phone Line # Trb
This screen is displayed when one of the telephone lines have failed.
The line that failed will be indicated by a number, 1 or 2.
4.1.6 NAC Output Trouble Screens
The screens below are displayed when one or more of the NAC outputs are in trouble. The output trouble
type can be an open or shorted supervision trouble, or an over current circuit trouble.
NAC TROUBLE 1234
The NAC TROUBLE screen is displayed when there are one or more
NACs in trouble. In this example all 4 circuits are in trouble because all 4
circuits are displayed.
NAC TROUBLE 23
In this example NACs 2 and 3 are in trouble. NACs 1 and 4 are normal.
4.1.7 Multiple Trouble Screens
When more than one trouble screen is active at the same time, each of the active screens will be
alternately displayed every 2 seconds so that all of the off normal trouble screens can be viewed.
4.1.8 Active Alarms and Trouble Screens
When there is at least one active alarm and additional troubles that are not zone related, the zone alarm
screen will be displayed every other screen no matter how many separate trouble screens are also active.
Each of the active trouble screens will be displayed in a rotation with the zone alarm screen.