HCA Series Installation Manual
Page 39 of 58
V2.15
5.4 Releasing Programming Options
The HCA panel provides water releasing and two agent releasing programming options. You must use
either the HCA-4 or HCA-8 if you are using releasing features as all releasing programming options
require the use of zones 1 through 4. Note that if you want to use a disconnect switch for the releasing
circuit, you must use the HCA-8! Both the water and agent releasing configurations use zones 2 and 3 for
cross alarm functions and zone 4 as a manual release alarm function; zone 5 of the HCA-8 is used for the
disconnect circuit (see section 5.4.4). The zone 1 function depends on the releasing option chosen as
detailed in the following sections.
Select option 4 from the main programming menu to reach the programming options for releasing.
5.4.1 Agent Release 1
The
Agent Release 1
option configures the panel for the cross zone releasing configuration shown in
figure 5.1. Figure 5.2 is a truth table that shows the cross alarm or manual release inputs that are needed
for agent releasing to occur.
PROGRAMMING MENU
4-Releasing, Nxt
Pressing 4 will select the releasing programming options. Pressing the
Next key will display the next programming menu option.
Set the release mode in the first screen.
Releasing Option
Agent Release 1
Use the down arrow to scroll through None, Water Release and the Agent
Release options. Once the desired release option is shown press the enter
key to accept the option.
Select the pre-discharge delay time before NAC 1 activates once cross zones 2 and 3 are both active.
Solenoid Cross
Alarm Delay: 30
Select solenoid delay time. Default is 30 seconds. Possible range is 30-60
seconds.
Select whether the Solenoid output should be automatically shut down after the shutdown timer expires.
Auto Shutdown
Solenoid(Y/N): Y
Choose the auto shutdown solenoid option. Select Y for the auto shutdown
solenoid feature. Select N to leave the solenoid active until system reset.
Press enter to accept displayed option on the screen. Default is Y (Yes).
If you select Y for Auto Shutdown Solenoid, the screen below will display to select the auto shutdown
time.
Solenoid Shutdwn
Time: 030
Select solenoid delay time. Default is 30 seconds. Possible range is
10-600 seconds.
Finally, select the output cadence pattern for NACs 2, 3 and 4. NAC 1 cadence is always continuous.
Release Pattern
Continuous
Use down arrow to scroll through cadence patterns for NACs 2, 3 and 4
with the releasing function. Once the desired cadence is shown press
enter key to accept cadence option.
The releasing cadence patterns are: