HCA Series Installation Manual
Page 54 of 58
V2.15
5.7 Panel Factory Default Setup
If there is ever a need to start over with the programming process the panel can be brought back to the
default factory programming settings. From the programming menu select option 7
PROGRAMMING MENU
7-Defaults, Nxt
Pressing 7 will select the programming options to restore the factory
default options. Pressing the Next key will take the display back to the
option 1 programming menu screen.
The screen below will be displayed after select option 7.
LOAD DEFAULTS
No
Select Yes and Enter to reload the manufacturer default settings.
Select No and Enter, or Esc to skip defaulting the panel.
5.7.1 Factory Default Settings
Default factory settings:
1) All zones are configured as FIRE alarm type zones with 1 second response time.
2) All zones are mapped to all 4 NAC outputs with continuous cadence pattern for alarm.
3) Dead shorts on zone inputs are interpreted as alarm, not trouble. (shorted mode = alarm)
4) The releasing features are deactivated.
5) The DACT is deactivated.
6) The installer access code is defaulted to 3333.
7) The user access code is defaulted to 2222.