HCA Series Installation Manual
Page 23 of 58
V2.15
It is necessary to enable the remote annunciator in the panel programming in order for the annunciator to
function as intended. See programming section 5.5 of this manual for instructions on adding a remote
annunciator to the HCA panel.
3.13.2 HCA-RA Specifications
Electrical Specifications
Operating Voltage: 16-26 VDC
Standby Current: 12 mA max
Alarm Current: 30 mA
Wiring Distance: 3,300ft max from FACP (using 18 gauge or larger diameter wire)
Maximum Annunciators per System: 1
Environmental Specifications
Operating Temperature: 32ºF
–120ºF (0ºC – 49ºC)
Humidity: 10%
– 93% non-condensing
Approvals
ETL Listed
Compatibility
Compatible with HCA series fire alarm panels.
Physical Dimensions
160mm x 160mm x 44 mm (6.3in x 6.3in x 1.75in)
Features
• 64-character backlit LCD display (4 lines with 16 characters on each line)
• Membrane Keypad
• Accepts user codes or fire fighter’s key
• Larger keypad buttons for system reset and silence
• RS-485 interface to panel
• On-board Piezo sounder audibly indicates alarm, trouble,
and supervisory events.
• Five status LEDs for alarm, supervisory, trouble, silence
and AC power conditions
• Wiring lengths up to 3300 ft. from the FACP
• ETL listed, complies with NFPA 72