background image

HCA Series Installation Manual 

Page 9 of 58 

V2.15 

2.  Controls and Indicators 

2.1  Front Panel User Control Buttons 

Acknowledge 

This function, abbreviated "Ack" on the keypad, is used to acknowledge an off normal condition such as an 
alarm or trouble condition. The acknowledge function tells the panel that building personnel or emergency 
responders are aware of the alarm, trouble, or supervisory condition. Acknowledging the alarm or trouble 
condition also silences the panel's sounder (PZT). 
 

Alarm Silence 

This function, abbreviated "Silence" on the keypad, is also known as "audible silence". Depending on the 
configuration  of  the  alarm  system,  this  function  will  either  silence  the  system's  notification  appliances 
completely,  or  will  silence  only  the  audible  alarm,  with  strobe  lights  continuing  to  flash.  Audible  silence 
allows for easier communication amongst emergency responders while responding to an alarm while still 
leaving the visual appliances on to indicate there is still an active alarm.  
 

Reset 

This function will reset the panel after an alarm condition. All initiating devices are reset, and the panel is 
cleared of any alarm conditions. If an initiating device is still in alarm after the system is reset, such as a 
smoke detector continuing to sense smoke, or a manual pull station still in an activated position, another 
alarm will be initiated.

 

 
 

2.2  LED Indicators: 

AC Power Green LED 

When this indicator is lit, power is being provided to the system from the building's electrical system and 
not from the backup battery. When the AC power condition is low or completely gone, the trouble indicator 
comes on and the AC power indicator goes off. If the AC power indicator is lit without any other indicators 
also lit, then the system is in a normal standby condition. If no LEDs are lit, there is no power source feeding 
the panel. 
 

Alarm Red LED 

This  Indicator  is  lit  when  an  alarm  condition  exists  in  the  system,  initiated  by  smoke  detectors,  heat 
detectors, sprinkler flow switches, manual pull stations, manual call points, or other initiating devices. Along 
with  the  indicator  on  the  panel,  notification  appliances  such  as  horns  and  strobes  are  also  activated, 
signaling  a  need  to  evacuate  the  building  occupants.  In  an  alarm  condition,  the  fire  alarm  control  panel 
indicates  where  the  alarm  originated.  The  alarm  panel  can  be  reset  once  the  device  which  initiated  the 
alarm is reset, such as returning the handle of a manual pull station to its normal position. 

 

Trouble Yellow LED 

When on steady or flashing, it means that a trouble condition exists on the panel. Trouble conditions are 
often  activated  by  a  contaminated  smoke  detector  or  an  electrical  problem  within  the  system.  Trouble 
conditions are also activated by a zone being disabled (disconnected from the system), low power on the 
backup battery, disabled notification appliance circuits, earth ground faults, shorted circuits or open circuits. 
The alarm panel's sounder will activate if a trouble condition exists. In a trouble condition, the panel displays 
the zone or devices causing the trouble condition. The trouble indicator goes out automatically when the 
situation causing the trouble condition is rectified or restores to normal. 

 

Silence Yellow LED 

The  silence  signal  indicates  that  a  trouble,  supervisory,  and/or  alarm  condition  has  been  silenced  by 
activating the silence key. 

 

 

 

Содержание HCA-2

Страница 1: ...8 HCA 8D Installation and Operation Manual Hochiki America Corporation 7051 Village Drive Suite 100 Buena Park CA90621 2268 714 522 2246 Corporate Headquarters 800 845 6692 Technical Support http www...

Страница 2: ...9 3 10 Relay Outputs 20 3 11 DACT Phone Lines 21 3 12 Remote Annunciator Model HCA RA 22 3 12 1 HCA RA Installation 22 3 12 2 HCA RA Specifications 23 3 13 Diagnostic LEDs 24 4 Control Panel Operation...

Страница 3: ...ing 38 5 3 4 Cadence Pattern Programming 38 5 4 Releasing Programming Options 39 5 4 1 Agent Release 1 39 5 4 2 Agent Release 2 42 5 4 3 Water Releasing 44 5 4 4 How to Install the Disconnect Switch o...

Страница 4: ...y components are all fully compatible with one another and that the full range of system functionality is supported by each device 1 1 Product Features The HCA panels have the following key features 2...

Страница 5: ...ne 10 ohms Initiating End of Line Resistor 4 7K ohms 1 2W 5 0400 01820 Standby Detector Current per zone 4mA maximum Maximum Detector Count per zone 20 detectors Initiating Cabling Type 18AWG Twisted...

Страница 6: ...detectors are located Smoke particles may be blown away from detectors by air outlets Smoke particles may be drawn into air returns before reaching the detector The amount of smoke present may be insu...

Страница 7: ...e amounts of dust dirt or high air velocity require more frequent maintenance A maintenance agreement should be arranged through the local manufacturer s representative Maintenance should be scheduled...

Страница 8: ...lure to do so can damage circuits Make all cable entries from the sides or top of the enclosure using the knockouts provided Route internal wiring around the outer edges of the enclosure and verify th...

Страница 9: ...letely gone the trouble indicator comes on and the AC power indicator goes off If the AC power indicator is lit without any other indicators also lit then the system is in a normal standby condition I...

Страница 10: ...ess frequently that a lower priority initiating device has been triggered such as a duct smoke detector The Supervisory indicator requires a Reset to clear 2 3 Local Piezoelectric PZT Sounder The piez...

Страница 11: ...A short circuit can result in arcing that could cause molten metal injuries to testing personal To minimize this possibility only qualified electrical technicians familiar with electrical hazards sho...

Страница 12: ...t If this happens the telephone company will provide advance notice so you can make the necessary modifications to maintain uninterrupted service If trouble is experienced with this equipment please c...

Страница 13: ...ncluded in the zone or NAC current calculations 2 Add in the total smoke detector standby current draw for each zone that is used and all standby accessory loads on NACs configured as auxiliary power...

Страница 14: ...ctors Standby Max Alarm 0 040A Number of Zone 2 Detectors Standby Max Alarm 0 040A Number of Zone 3 Detectors Standby Max Alarm 0 040A Number of Zone 4 Detectors Standby Max Alarm 0 040A Number of Zon...

Страница 15: ...the cabinet since this area is intended for batteries only 3 6 AC Power Connection WARNING To reduce the risk of electrical shock make sure that all power has been turned off or disconnected prior to...

Страница 16: ...attery fault LED on the main circuit board will show steady in such a condition When the green battery LED is on steady it shows that the battery condition and connections are normal See Figure 3 6 be...

Страница 17: ...V door holder circuits Figure 3 7 shows NAC 1 wired as a class B NAC Observe the polarity of the wiring and the placement of the 10k end of line EOL resistor located at the very end of the class B wir...

Страница 18: ...arm style B or a trouble condition style C Wire the smoke detector positive terminals to the HCA terminal labeled and the negative smoke detector terminals to the HCA terminal labeled as shown in figu...

Страница 19: ...dd yyyy HCA SERIES WIRING DIAGRAM P N 1700 05660 Doc HA 03 343 Rev V2 XX DATE mm dd yyyy 4 Class B Outputs Special Application NAC 2 5 amps max Regulated Auxiliary Power 1 0 amps max 10 K resistor pa...

Страница 20: ...le relays carry the same voltage and current ratings The relays are rated 3 amps at 30VDC power factor 0 4 1 0 NO NC C NO NC C NO NC C RELAY 1 ALARM RELAY 3 TROUBLE NO NC C NO NC C RELAY 2 Dry Contact...

Страница 21: ...tails IMPORTANT The HCA DACT must be the first device connected on the incoming telephone lines and all local premises phones must be located on the phone wiring identified as Phone Ring and Phone Tip...

Страница 22: ...mote Annunciator Model HCA RA 3 13 1 HCA RA Installation GND GND 485 GND GND 485 BUZ ZER 1 1 6 24VDC RS485 HCA RA Remote Annunciator 485 GND HCA Control Panel HCA FACP Wire Runs Up to 3300 Feet From F...

Страница 23: ...rs per System 1 Environmental Specifications Operating Temperature 32 F 120 F 0 C 49 C Humidity 10 93 non condensing Approvals ETL Listed Compatibility Compatible with HCA series fire alarm panels Phy...

Страница 24: ...Diagnostic LED Locations Designation Color Description D115 Green This LED flickers when the panel is working normally D116 Amber When this LED is lit it indicates trouble with the panel s internal o...

Страница 25: ...eypad Important Note If the system is left idle in a menu without any activity for 5 minutes the system will automatically exit the menu 4 1 LCD Display Screens All status and operations display scree...

Страница 26: ...ty followed by supervisory and then trouble 4 1 4 Zone Alarm and or Trouble Screens The screen below is displayed when at least one zone is in trouble or alarm Z1 2 3 4 5 6 7 8 N A T N S D N A This sc...

Страница 27: ...t Trouble Screens The screens below are displayed when one or more of the NAC outputs are in trouble The output trouble type can be an open or shorted supervision trouble or an over current circuit tr...

Страница 28: ...ns in the system the user can silence the panel PZT by pressing the acknowledge key Acknowledge has no effect on the NACs or system LEDs 4 3 Login Screen The login screen is activated whenever the use...

Страница 29: ...ustment is the same for both the user and installer menu Pressing the Next key will display the next installer menu option INSTALLER MENU 3 Walk Test Nxt Pressing 3 will select the walk test function...

Страница 30: ...elow Choose American or European date time format DATE TIME TYPE 1Amer 2Euro Select 1 for North American format Select 2 for European format DATE 00 00 00 TIME 00 00 am At this screen enter the date a...

Страница 31: ...enus option 4 The event history can only be cleared from the installer menu 4 9 1 Viewing Event History From the user or installer main menu select option 4 to view the event history The next screen d...

Страница 32: ...ew seconds while the history is erased You will then be returned to the installer main menu 4 10 Disabling Circuits 4 10 1 Disabling or Enabling Zones Zones can only be disabled from the installer men...

Страница 33: ...the N to Y by pressing the Yes 9 key and then press the Enter key The screen below will display briefly before returning to the main installer menu Manual DACT test Started This screen displays brief...

Страница 34: ...tion After selecting 1 for User Codes you will see SELECT TYPE USER 1 USER 2 ADMIN Select 1 to edit the user code Select 2 to edit the installer code If you select 1 you will see USER PASSWORD ENTER C...

Страница 35: ...riggered the NAC are also silenceable If both a non silenceable zone and a silenceable zone are active and have triggered a silenceable output the output will be non silenceable If only silenceable zo...

Страница 36: ...nt to select No to the Shorted Z Alarm programming question If you select no zones that are completely shorted will be interpreted as being in trouble and not alarm This programming option defaults to...

Страница 37: ...able Circuits 1 2 and 4 are not silenceable 5 3 2 3 Assigning Outputs to the Resettable Auxiliary Power Function NACs that will be used as resettable 24VDC power need to be selected in the AUX RESETTA...

Страница 38: ...s 1 and 2 are non silenceable NOTE If you want to select which relays activate when an alarm or supervisory event occurs go to the zone programming menus to map the relays to the individual zones 5 3...

Страница 39: ...will display the next programming menu option Set the release mode in the first screen Releasing Option Agent Release 1 Use the down arrow to scroll through None Water Release and the Agent Release op...

Страница 40: ...NAC 1 and the releasing indicator NAC 3 Zone 4 is a manual release zone Manual releasing switches must be wired to zone 4 so that when one or more release switches are activated agent releasing occur...

Страница 41: ...n Inputs Normal Standby Common Alarm and Release Common Alarm Common Alarm Common Alarm and Release Common Alarm and Release Common Alarm and Release Manual Release Cross Zone B Cross Zone A Common Al...

Страница 42: ...releasing occurs immediately As soon as zone 4 activates NAC 4 activates indicating general alarm There is no pre discharge delay period for manual release so NAC 2 activates immediately along with N...

Страница 43: ...auto shutdown solenoid option Select Y for the auto shutdown solenoid feature Select N to leave the solenoid active until system reset Press enter to accept displayed option on the screen Default is Y...

Страница 44: ...eleasing Option Water Release Use the down arrow to scroll through None Water Release and Agent Release options Once the desired release option is shown press the enter key to accept the option Select...

Страница 45: ...cause a water release for single interlock and may occur for double interlock depending on the state of the interlock zone 1 Zone 4 is a manual release zone Manual releasing switches must be wired to...

Страница 46: ...ease Inputs Outputs Single Interlock Truth Table Normal Standby Common Alarm and Release Common Alarm Common Alarm Common Alarm and Release Common Alarm and Release Common Alarm and Release Manual Rel...

Страница 47: ...w to connect the disconnect switch to the HCA You will need a Hochiki America SOM R DS Disconnect Switch for this application The disconnect switch is connected in line with the releasing circuit NAC...

Страница 48: ...4 zone HCA may be used for applications where a disconnect switch is not required ALWAYS confirm with your AHJ before installing the system When the disconnect switch is operated it will result in tw...

Страница 49: ...master enable flag for the DACT which allows the installer to enable or disable the DACT easily without changing any other DACT programming options Note that the panel will not be in trouble if you tu...

Страница 50: ...lue is 180 minutes 5 6 4 Edit Accounts There are 4 reporting accounts within the DACT which can be used for reporting the various reportable events to different receivers and or phone numbers See tabl...

Страница 51: ...restores to the central station Report Alarms Y N Y Select Y if you want alarms reported to this account Select N if you do not want alarms reported 5 6 4 4 Supervisory Reporting Filter The superviso...

Страница 52: ...municate using the primary phone number In addition to the digits 0 through 9 you can also insert commas that will generate pauses between the digits being dialed This might be useful when you need to...

Страница 53: ...2 followed by the Enter key 5 6 5 1 Dialing Format Select which dialing format you would like this line to use You can chose to only use touch tone dialing a combination of touch tone and pulse dialin...

Страница 54: ...creen The screen below will be displayed after select option 7 LOAD DEFAULTS No Select Yes and Enter to reload the manufacturer default settings Select No and Enter or Esc to skip defaulting the panel...

Страница 55: ...10 Fire Drill Begin Fire Drill FI 0 1 604 0 Fire Drill End Fire Drill FK 0 3 604 0 AC Power Trouble Trouble AT 0 1 301 0 AC Power Trouble Restore Trouble AR 0 3 301 0 Battery Charger Trouble Trouble...

Страница 56: ...224 43mA draw 24V 20 NS6 100 150mA maximum 24V 20 NS4 100 150mA maximum 24V 20 PULL STATION HPS SAK HPS DAH Conventional Manual Pull Station 25 HPS SAH HPS DAK Conventional Manual Pull Station 25 7 2...

Страница 57: ...worst case current consumption for the appliance models chosen and make sure the total current for all appliances does not exceed the maximum current rating of the HCA NAC circuit Gentex Environment...

Страница 58: ...quipment which has been repaired by others abused improperly installed altered or otherwise misused or damaged or exposed to conditions outside the products specifications in any way Unless previously...

Отзывы: