Mobile Foam Unit
Version 50-150
14 of 36
5
Water and operation conditions
5.1 Water supply
The suction inlet requires cold and clean water, free of suspended matter.
Preferably, fill the tank with clean tap water
. Dirt, germs or algae may affect the function of
the solenoid valves or the ability of the foaming agent.
To prevent germs and algae, you may add an algaecide concentrate in appropriate dosage
to the water tank.
Suction from external water sources (pond, pool, river, etc.) with floating filter only.
Range of water temperature: + 3 to 38 ° Celsius, maximum suction lift: app. 2.5 meters.
5.2 When mounted stationary
…
Observe the following criteria regarding the place of installation:
Ventilation of engine exhausts and fresh air supply must always be ensured.
The air-cooled engine radiates a significant amount of heat when running.
Ambient temperature should stay b3 to +45° C. Keep the temperature rise of longer
operating times in mind.
The place of installation has to be dry, frost-safe and free of dust.
The unit must be leveled with 5 cm minimum distance to the ground.
The system should be easily accessible from all directions for maintenance and cleaning.
No heat-sensitive objects in the immediate vicinity of the exhaust system.
No flammable gases or liquids may be stored in the same room.
5.3 When mounted on vehicles
…
The same criteria as above (5.2) apply. Pay additional attention to the following points:
Do not park the vehicle in frost-prone places or for long periods in blazing sun.
Keep as much distance as possible from the water tank to the device.
The MFU should be operated in horizontal position. Place the vehicle on level ground
wherever possible.
ATTENTION
The unit must be kept absolutely free of frost. At temperatures
below + 3° Celsius, water-filled areas of the system are at risk
of frost damage.
Suck pressure-free water only. When using a pressurized
hydrant, refill the water tank directly.