Initial start up
Pleas carry out the following preparations after complete and correct installation:
1. Fill the fuel tank (10) and check the engine oil level according to the instructions of
the engine manufacturer.
2. Check the oil levels of pump (page
31
, section
11.6.1
) and gear (page
33
, section
11.6.4
).
3. Check the pressure of the pulsation damper at its valve (12) and adjust if necessary.
(see page
32
, section
11.6.3
). Correct pressure =
7,0 bar / 102 PSI
4. Turn the ball valve lever (6) into tank position. When using the floating filter, turn the
lever (6) into external position. Bring the filter to water and connect the hose with the
suction intake (9) of the MFU (see page
22
, section
7.9
and
7.10
).
5. Connect the battery. The MFU is shipped with disconnected ground terminal. Use a
proper wrench (size 10). CAUTION: HIGH POWER VOLTAGE !
6. Fill the water tank (when equipped) with clean water.
7. Fill the foam agent tank (4) with proper concentrate (see page
20
, section
7.7
).
8. Turn on the ignition and start the engine (see page
18
, section
7.3
).