1.
In the setting menu, when the colon is not flashing, press [▲], [▼] button to change the
function number; when the colon is flashing, press [▲], [▼] button to change the data, press
and hold
[
▲
],[
▼
]button for
more than 1 second, the data will be increased or decreased in
rapid succession.
2. Press [▲], [▼] button in the help menu to change the content of the corresponding help
prompt information. In bypass operation, and the setting and help menu is not entered, the
motor running current is displayed. Press
the [▲], [▼] button at this time to select and display
the inspecting power of the motor or the thermal balance coefficient of the motor overload.
When the indicated value of the thermal balance coefficient is greater than 100%, overload
protection will be performed.
The motor can be started only when the setting keyboard of function parameter FB is valid,
otherwise, the button cannot start the motor
When the setting keyboard of function parameter FB is valid, the keyboard can be stopped.
Otherwise, the machine can not be shut down by pressing this button, and the function is
"Reset" in the fault state.
5.3 Function and parameter table
Function code
Name
Setting range
Factory
value
Description
F0
Starting voltage
30-80%
30%
Voltage ramp mode is valid;
Starting voltage of current mode is 40%
F1
Soft starting time
02-60S
16S
Voltage mode is valid
F2
Soft stopping time
00-60S
2S
Free stop when set to 0
F3
Starting over-current
Protection time
00-60S
00S
During starting the motor, when the time of more
than 3 times the rated current exceeds the setting
value of this parameter, the over-current
protection will be activated
F4
Programming delay
00-999S
00S
For programmable relay output
F5
Starting current limit
50-500%
280%
Current limiting mode is valid;
The max. current limit in voltage ramp mode is
400%
F6
Max. working current
50-200%
100%
Relative to the value of rated current FP
Содержание HRS Series
Страница 1: ...HRS Series High Performance Soft Starter Operation Manual V1 0 HNC Electric Limited ...
Страница 8: ... 8 Safety Precautions ...
Страница 15: ... 15 4 Wiring 4 1 Application wiring diagram 4 1 1 Main circuit connection diagram of soft starter ...
Страница 17: ... 17 4 1 3 Primary and secondary wiring diagram ...
Страница 18: ... 18 4 1 4 Wiring diagram of relay and remote control ...