- 21 -
Function code
Name
Setting range
Factory
value
Description
F7
Under-voltage
prote4ction
49-90%
70%
Under voltage protection when it is lower than the
set value, when it is set to 49%, turn off the function
F8
Over-voltage protection
100-131%
120%
Over-voltage protection when higher than the set
value, when set to 131%, turn off the function
F9
Starting mode
00-06
01
00 current limit; 01 voltage; 02 sudden jump +
current limit;
03 sudden jump + voltage; 04 current ramp; 05
double closed loop; 06 full voltage
FA
Protection level
00-05
02
00 Primary; 01 Light load; 02 Standard;
03 Heavy load; 04 Advance
FB
Control method
00-06
04
00 Keyboard;
01 Kexternal control;
02 external control;
03 external c communication;
04 ke communexternal control;
05 ke communication;
06 communication
FC
Parameter modification
allowed
00-02
01
00: It is forbidden to modify any parameters except
the setting item FC; 01: It is forbidden to modify the
parameters of F4, F5, F6, FD, FE, FU, FL, FM, FN;
02: It is allowed to modify the parameters of all
functions
FD
Communication
address
0-64
00
Used for MODBUS local slave address setting
FE
Programming output
00-19
06
Used to define
③
-
④
terminal output
See the description in section 5.4 for details
FF
Turn-stop current limit
30-100%
80%
FP
Rated current valve of
motor
Rated value
Used to enter the nominal rated current value of the
motor
FU
Bypass delay
1-40S
3S
Used to set the time of bypass delay
FL
Three-phase
imbalance
00-01
01
00:Three-phase imbalance prohibited, 01: Three-
phase imbalance allowed
FM
Current ratio
50-150%
100%
Used to adjust the display current value
FN
Voltage ratio
50-150%
100%
Used to adjust the display voltage value
Remarks:
1. The max. working current of setting item F6 refers to the max. current that allows the motor to run continuously based on
the FP setting value. If this value is exceeded, inverse-time thermal protection will be performed.
2. If there is no key operation for more than 2 minutes in the setting state, it will automatically exit the setting state.
3. Parameters cannot be set during soft start and soft stop, and parameters can be set in other states.
4. Press the[YES] button to power on, and the set parameters can be restored to factory values.
Содержание HRS Series
Страница 1: ...HRS Series High Performance Soft Starter Operation Manual V1 0 HNC Electric Limited ...
Страница 8: ... 8 Safety Precautions ...
Страница 15: ... 15 4 Wiring 4 1 Application wiring diagram 4 1 1 Main circuit connection diagram of soft starter ...
Страница 17: ... 17 4 1 3 Primary and secondary wiring diagram ...
Страница 18: ... 18 4 1 4 Wiring diagram of relay and remote control ...