- 32 -
7. MODBUS Communication Protocol
7.1 Overview about Modbus RTU communication protocol
Modbus is a serial asynchronous communication protocol. Its physical interface is RS485. Modbus is designed for
modiconPL C and has the structural characteristics of PLC. In Modbus network control, the soft starter can be compared
to a PLC for reading and writing. The soft starter maps the start-stop control, status information (current, fault, etc.) and
function parameters to the holding register area (4XXX). It is read and written through the PL master station when in use.
7.1.1 Electrical interface
RS485 half duplex
Communication parameters:Baud rate: 9600; 8 data bits; no parity bit; 1 stop bit. .
7.1.2 Communication data format
Data format
Address code
Function code
Data area
CRC check
1 byte
1 byte
N bytes
2 bytes
7.2 Related setting of soft starter
7.2.1 Register address
Register address
Operation code
Description of register function
40001
06
Control word
40002
03
Status word
40003
03
Current average value
40004
03
Fault code
40256-40273
03&06
Function code of soft starter
40274
03
Specification of rated current
40275
03
Specification of rated voltage
40290
03
Power voltage value
(1) Register not listed above is illegal and cannot be read or written. Otherwise, the slave station will report an exception
code to the controller.
(2) All data addresses are referenced to 40,000. i.e, the address of the coil relay 40001 is 0001, and the address of
402567 is 0100 (hexadecimal).
Содержание HRS Series
Страница 1: ...HRS Series High Performance Soft Starter Operation Manual V1 0 HNC Electric Limited ...
Страница 8: ... 8 Safety Precautions ...
Страница 15: ... 15 4 Wiring 4 1 Application wiring diagram 4 1 1 Main circuit connection diagram of soft starter ...
Страница 17: ... 17 4 1 3 Primary and secondary wiring diagram ...
Страница 18: ... 18 4 1 4 Wiring diagram of relay and remote control ...