8.2 Daily maintenance of soft starter
●
Prevent electric shock and dust
If there is too much dust, the insulation level of the soft starter will be reduced and the soft starter may not work properly.
a. Creepage and arcing in the primary circuit will endanger the equipment;
b. Leakage, short circuit in the secondary circuit, control failure;
c. The thermal resistance of the radiator increases, and the temperature of the SCR increases.
●
Clean up dust
a. Use a clean and dry brush to gently brush away the dust;
b. Blow off the dust with compressed air.
●
Condensation
If frost is formed, the insulation level of the soft starter will be reduced, and the soft starter may not work properly.
a. Creepage and arcing in the primary circuit will endanger the equipment;
b. Leakage, short circuit in the secondary circuit, control failure;
c. Strengthen the seat corrosion of metal parts.
●
Dry
a. Drying with electric blowing or electric furnace;
b. Dehumidification in the power distribution room.
Schedule 1. Application field
Mechanical type
Load type
Starting mode
Value setting
Rise time
Voltage
Current
Heavy
load
Voltage (%)
Current (%)
Centrifugal pump
Standard load
•
250
5
Fan
Heavy load
•
•
400
40
Compressor (piston type)
Standard load
•
300
10
Compressor (centrifugal type) Standard load
•
30
20
Conveyor machine
Standard load
•
250
10
Blender
Standard load
•
•
350
5
Ball mill
Heavy load
•
•
70
400
50
Crusher
Heavy load
•
60
45
Содержание HRS Series
Страница 1: ...HRS Series High Performance Soft Starter Operation Manual V1 0 HNC Electric Limited ...
Страница 8: ... 8 Safety Precautions ...
Страница 15: ... 15 4 Wiring 4 1 Application wiring diagram 4 1 1 Main circuit connection diagram of soft starter ...
Страница 17: ... 17 4 1 3 Primary and secondary wiring diagram ...
Страница 18: ... 18 4 1 4 Wiring diagram of relay and remote control ...