- 38 -
Schedule 2. Specification and parameter of peripheral accessories
HRS Series Soft Starter( 5.5KW~ 55KW )
Model
Rated
power
(kw)
Rated
current
(A)
SCPD
specification
Supporting circuit
breaker
model(QF)
Supporting
bypass
contactor
model
(KM)
Specification of
primary cable
Remark
HRS-5R5-B-G3
5.5
11
RS0-20
TGM1-63L /16
CJ20-16
2.5mm
2
cable
For
55KW
and
below, use cable to
lead out the wiring,
the method is six in
and
three
out.
Rated power rated
current refers to the
max. value of the
soft starter.
HRS-7R5-B-G3
7.5
15
RS0-30
TGM1-63L /25
CJ20-16
4mm
2
cable
HRS-011-B-G3
11
23
RS0-50
TGM1-63L /32
CJ20-25
6mm
2
cable
HRS-015-B-G3
15
30
RS0-80
TGM1-63L /40
CJ20-40
10mm
2
cable
HRS-018-B-G3
18.5
37
RS0-80
TGM1-63L /50
CJ20-40
10mm
2
cable
HRS-022-B-G3
22
43
RS0-80
TGM1- -63L/63
CJ20-63
16mm
2
cable
HRS-030-B-G3
30
60
RS0-100
TGM1-63L /80
CJ20-63
25mm
2
cable
HRS-037-B-G3
37
75
RS0-150
TGM1-63L/100
CJ20-100
35mm
2
cable
HRS-045-B-G3
45
90
RS0-200
TGM1-63L/125
CJ20-100
35mm
2
cable
HRS-055-B-G3
55
110
RS0-200
TGM1-63L/160
CJ20-160
35mm
2
cable
Note: The specification parameter list of peripheral accessories is for reference
HRS Series Soft Starter(
75KW~320KW
)
Model
Rated
power
(kw)
Rated
current
(A)
SCPD
specification
Supporting circuit
breaker model(QF)
Supporting
bypass
contactor model
(KM)
Specification of
primary cable
Remark
HRS-075-B-G3
75
150
RS0-300
TGM1-225U200
CJ20-250
35mm
2
cable
For
75KW
and
above, the cable is
used to lead the
wiring,
and
the
method is six in
and
three
out.
Rated power rated
current refers to
the max. value of
the soft starter.
HRS-090-B-G3
90
180
RS0-320
TGM1-225L7225
CJ20-250
30x3mm
2
copper wire
HRS-115-B-G3
115
230
RS0-480
TGM1-400U315
CJ20-250
30x3mm
2
copper wire
HRS-132-B-G3
132
260
RS0-600
TGM1-400U315
CJ20-400
30x4mm
2
copper wire
HRS-160-B-G3
160
320
RS0-600
TGM1-400L7350
CJ20-400
30x4mm
2
copper wire
HRS-185-B-G3
185
370
RS0-700
TGM1-400U400
CJ20-400
40x4mm
2
copper wire
HRS-200-B-G3
200
400
RS0-700
TGM1-630L7500
CJ20-400
40 x 4mm
2
copper wire
HRS-250-B-G3
250
500
RS0-800
TGM1-630U630
CJ20-630
40x5mm
2
copper wire
HRS-280-B-G3
280
560
RS0-1000
TGM1-63017630
CJ20-630
40x5mm
2
copper wire
HRS-320-B-G3
320
640
RS0-1000
TGM1-800U700
CJ20-630
40x5mm
2
copper wire
Note: The specification parameter list of peripheral accessories is for reference
Содержание HRS Series
Страница 1: ...HRS Series High Performance Soft Starter Operation Manual V1 0 HNC Electric Limited ...
Страница 8: ... 8 Safety Precautions ...
Страница 15: ... 15 4 Wiring 4 1 Application wiring diagram 4 1 1 Main circuit connection diagram of soft starter ...
Страница 17: ... 17 4 1 3 Primary and secondary wiring diagram ...
Страница 18: ... 18 4 1 4 Wiring diagram of relay and remote control ...