24 (148)
The PLC has been stopped.
The PLC has been successfully stopped.
A new I/O mapping list has been saved.
A new I/O mapping list has been successfully saved to the PLC.
A new diagram has been saved.
A new diagram has been successfully saved to the PLC.
Task cycle is being maintained again.
This message appears after this message, when the task cycle is being maintained again.
Portal communication error
<x>
A communication error has occurred while exchanging data with the portal. Possible error codes:
-2
Out of memory
-3
The internal data queue has overflown, because data was produced faster than it could be processed.
If you see an error code that is not on the above list, please contact the customer support.
Task cycle has been violated.
The given task cycle of the PLC has been violated at least once. This is probably caused by a cycle
time that is too short in relation to the complexity of the program. Please check the duty cycle of
the PLC in the status bar of the editor. When the task cycle can be maintained again, this
message will appear.
Stopping PLC due to missing licence.
Since the device does not have a valid HMS Hub licence, the PLC runs in demo mode and is now
being stopped after a runtime of four hours.
Exception in task:
<message>
A fatal exception has occurred inside the PLC task. A detailed description is provided. The PLC is
stopped and the device will be restarted by the watchdog after a short time. This should not
happen. Please contact the customer support.
3.6
Live View
Via the Live View function it is possible to see the current state of the PLC right in the diagram
view. After clicking on the Live View button on the toolbar the HMS Sequence editor will start
showing the actual value of each output port in a small blue box next to the port.