106 (148)
Interval
Interval in which the IEC 60870-5-104 Client driver sends its requests. The more values you define, the
more time the driver will need for the requests and the greater should the interval be. Note that if the
interval is too short to update all values, a warning message will be shown on the event log. In this case
you should increase the interval.
Please note that the IEC 60870-5-104 client will only be available if your Edge gateway device has
a valid IEC 60870-5-104 client licence.
Event Log Messages
The following section describes the messages that the IEC 60870-5-104 Client driver may log to
the Event Log. All messages are prefixed with the text
IEC 60870-5-104 client driver:
.
•
Updated output at address<information object address>.
The output with the given information object address has been successfully updated. This
message will only be shown, if updating the same output has failed before.
•
The interval is being maintained again
.
This message appears after this message, when the interval is being maintained again.
•
The interval has been violated.
The driver was still busy updating the values when a new cycle should be started. You
should probably increase the interval.
•
Could not update output at address
<information object address>
. Error code
<code>
,
error message
<message>
Updating the output object with the given information object address failed. This should not
happen. Please contact the customer support.
•
Portal communication error
<error code>
A general error has occurred while exchanging data with the portal. Possible error codes:
-2
Out of memory
-3
The internal data queue has overflown, because data was produced faster than it could be processed.
If you see an error code that is not on the above list, please contact the customer support.
Licensed Software
The IEC 60870-5-104 library by SystemCORP Embedded Technology Pty. Ltd. has been used to
implement the IEC 60870-5-104 interface. Website:
IEC 61850
The IEC 61850 interface can be configured through this form.
The standard series IEC 61850 (Communication networks and systems for power utility
automation) comprises mainly: Information models (logical nodes and DataObjects),
configuration of a system, the information, the communication used, and the communication
protocols. The standard series IEC 61400-25 (Communication networks for wind power systems)
is an extension of IEC 61850. The HMS Hub firmware supports both standards with the MMS
mapping.
The HMS Hub firmware implements IEC 61850 Client, Server, Publisher and Subscriber. The IEC
61850 inputs and outputs are automatically configured by an interpretation of the corresponding
SCL files for the server and/or the client role.
Notes:
1.
The application of the IEC 61850 requires a good understanding of the core standards of the
IEC 61850 series.
Anybus Edge Gateway Reference Guide
SCM-1202-154 1.0 en-US