49 (148)
Error Log Messages
The following section describes the messages that the system time manager and the SNTP client
may log to the Event Log. All Messages are prefixed with the text
System time manager:
or
SNTP
client:
.
•
Running
The system time manager is now running.
•
System clock updated via SNTP
The system clock (and if available the real-time clock) has/have just been updated with the
time gotten via SNTP.
•
System clock updated from RTC
The system clock has just been updated with the time from the real-time clock.
•
Could not get exclusive access to clock(s)
The system time manager could not get exclusive access to the system clock and (if
available) the real-time clock. Thus the system clock could not be set or the real-time clock
could not be read.
•
Daylight saving time rules will be used up within the next two years
The firmware of your Anybus Edge device includes daylight saving time rules for a limited
time period. New rules will be added with new firmware versions. This message indicates
that the rules will be used up within the next two years. You should apply a firmware
update to get new rules.
•
SNTP client error:
<message>
The SNTP client has returned the shown error message.
•
RTC not found
The device should feature a real-time clock, but it cannot be accessed.
•
Could not write to RTC:
<message>
The real-time clock could not be written. The message shows an error message returned by
the real-time clock driver.
•
Could not read from RTC:
<message>
The real-time clock could not be read. The message shows an error message returned by
the real-time clock driver.
•
Could not read daylight saving time file
The daylight saving time file for this time zone is missing or corrupted.
•
No daylight saving time rule found for the current time
No daylight saving time rule could be found for the current time. That means either that the
daylight saving time rules are outdated or that the Anybus Edge's time is set wrongly.
•
DNS error (<error code>) for server <server name/IP>
The SNTP client could not determine the IP address of the server with the given name. The
message also shows the error code returned by the TCP/IP stack.
•
Could not open socket for server
<server name/IP>
The SNTP client could not open a UDP socket in order to contact the time server with the
given name or IP address.
Anybus Edge Gateway Reference Guide
SCM-1202-154 1.0 en-US