Service Menu - Continued
139 Bell Test
By selecting
Bell Test
the panel will activate the buzzer,
internal siren(s) and external siren(s) in sequence.
Note:
You will be prompted on the display to go outside to hear the external
siren(s).
When you select
Zone Resistance
you can interrogate, by
default, each Alarm and Entry/Exit zone to determine its loop
resistance - should be used with the Remote Maintenance
feature in
SmartLink700
to track any trends that would suggest
corrosion build-up etc.
Note:
You will need V2.1+ software in your 10-Zone expanders to see their
loop resistances.
Default Eng. Code - 4567 Default User Code - 1111 (Irl) 1234 (UK)
13 ENG. TOOLS contd.
!
!
!
!
145 Part Set B ?
144 Part Set A ?
143 Quick Arm ?
142 Full Set ?
141 Unset ?
14 ENG. ARM/DISARM
Used to arm the panel from within engineer mode. Once an
item is selected the panel will automatically exit the engineer
mode and start arming the panel. Once armed in this fashion
the panel can then be disarmed once by the engineer code.
This enables full testing of the system by an Engineer without
having to know somebody’s User code.
15 DEFAULTS MENU
16 FIRMWARE UPDATE
Used to default the panel and other devices back to their
factory settings. There are seven default options to choose
from so that different areas of the system can be defaulted
without affecting other areas.
Default all?
defaults all devices on the system. Then there is
Default Users?
which defaults the User and Engineer codes
(but not their names, options etc.)
Default Comms?
defaults
the dialler and any such communications device.
Default
Keypads?
and
Default Expandr?
defaults keypads and
expanders.
Default ID Bus?
defaults any devices on the point
ID bus system and finally
Default RF System?
defaults
wireless devices.
Note:
please refer to the back of this manual for details of panel default
settings.
In the first instance, you need to be connected to
SmarkLink
to
update your firmware (i.e your panel’s software).
Select
Firmware Update
, you will then be prompted to key-in
the
Mfg. Code:------
(Manufacturer’s Code). By default it is
4567. Therefore, key-in 4567 followed by YES. You will then be
prompted to key-in the
User Code:------
. When that is done,
the display should say
Start File Transfer.
Next, go to the
relevant page in the
SW-1070
section of
SmartLink
and select
File Transfer
. This starts updating the firmware.
Note:
If you have already commissioned your alarm system (e.g. Zone
descriptions, timers, devices etc.); this feature DOES NOT affect its
configuration.
151 Default All?
152 Default Users?
153 Default Comms?
154 Default Keypads?
155 Default Expandr?
156 Default ID Bus?
157 Default RF?
58
1310 Zone Resistance
Содержание SW-1070
Страница 1: ... for V3 3 Software www hkcsecurity com Security Safe Secure SecureComm compatible Installation Manual ...
Страница 117: ...Default Eng Code 4567 Default User Code 1111 Irl 1234 UK Appendix B 117 GPRS GSM SMS DATA Voice ...
Страница 118: ...Broadband SMS DATA or Appendix B Default Eng Code 4567 Default User Code 1111 Irl 1234 UK 118 ...
Страница 120: ...Default Eng Code 4567 Default User Code 1111 Irl 1234 UK 120 Appendix Appendix Appendix B SMS Voice Standard Mobile ...