ADI CD Boiler – Technical Manual
40
15. SAFETIES
These are the safeties included in the boiler:
Cause for safety
activation
Safety
component of
the boiler
Boiler restart
No flame
Ionization
electrode
Manual reset
Fan failure/air
passage obstruction
Air pressure
switch
Manual reset
Overheating
Safety
overheating
thermostat
> 90ºC+- hysteresis: the regulation stops the boiler.
> 95ºC: boiler lockout, error on the display. Manual reset.
> 100ºC: fan at the maximum power to cool down the boiler.
> around 103ºC: lockout, other error on the display, manual reset.
No gas
Minimum gas
pressure switch
Automatic reset
Low water flow
through the boiler
Boiler control unit
Safety 1: if the Delta T in the boiler is higher than the maximum
Delta T, the power drops by 20%.
Safety 2: if it overcomes “the maximum Delta T” + 8ºC, the boiler
operates at the minimum power.
Safety 3: if it overcomes a higher value, the boiler stops and an error
message appears on the display E 110/428.
Lack of water
pressure in the circuit
Pressure sensor
The boiler stops for safety if pressure in the circuit is around 0.8 bar.
16. BOILERS IDENTIFICATION LABEL
The adhesive identification label of each boiler is placed inside the boiler, stuck in the front of the higher water
collector of the boiler heat exchanger.
In order to visualize it, you have to lift up the top casing of the boiler and remove the front casing. The label
shows the boiler serial number, model and the rest of technical data.
Another one is placed at the lateral panel of the boiler.
BOILER FRONT VIEW
Содержание ADISA ADI CD 105
Страница 1: ...TECHNICAL MANUAL OF INSTALLATION USE AND MAINTENANCE 4 2020 uk ADI CD CONDENSING BOILER...
Страница 7: ...ADI CD Boiler Technical Manual 7 Models ADI CD 200 and higher...
Страница 31: ...ADI CD Boiler Technical Manual 31 12 1 Electric drawing ADI CD 70 750...
Страница 32: ...ADI CD Boiler Technical Manual 32 12 2 Electric drawing ADI CD 850 950...
Страница 69: ...www adisaheating com ADISA HEATING HIPLUS AIRE ACONDICIONADO S L...