ADI CD Boiler – Technical Manual
44
17.6 Chimneys
The flue outlet, according to the current rules, must ensure a correct evacuation of the burnt gases, without
backward flows and without producing condensate. The natural draught of the chimney must evacuate the burnt
gases from the boiler flue outlet.
17.6.1 Chimney sizing
The internal diameter depends on:
- Heat input of the boilers, type, number of boilers installed and water working temperatures.
- Type of gas.
- Chimney: vertical height, horizontal length (minimum slope: 3 to 5%).
- Number of elbows and their angles (they should be reduced to the minimum).
- The chimney material and if it is insulated or not.
If several boilers are connected to the same chimney, it is important to consider the distance between them and
the dimensions of the flue header.
The base of the vertical chimney must include a drainage pipe to evacuate the condensate.
With regard to boilers, these are the data to be considered for calculation:
-
Values of CO2, for Natural Gas: it is recommended to adjust at 8,1% of CO2, for all the boilers
Models
Range CO2 (%) for Natural Gas
ADI CD 105 to 200
7.3 - 9.1%
ADI CD 250 to 325
7.3 - 8.5%
ADI CD 400 to 750
7.3 - 8.8%
ADI CD 850 to 950
7.6 - 8.6%
- Flues temperature:
Flues temp.
MAXIMUM POWER
MINIMUM POWER
Average Water temperature
High ( 70ºC)
Low ( 40ºC)
High ( 70ºC)
Low ( 40ºC)
Flues Temp.
70 - 80ºC
50 - 60ºC
60-70ºC
40ºC
- Residual pressure at the flues output of the boiler:
Model
ADI CD
Ø flue outlet of the
boiler; External
diam. (mm)
MAXIMUM POWER
MINIMUM POWER (*)
Power Input
kW
Residual Pressure
(Pa)
Power Input
kW
Residual Pressure
(Pa)
70
150
72,7
21
21,8
2,5
85
150
87,7
18,9
26,3
7,5
105
150
107
45
32
40
120
150
123
32,4
37
5
175
150
166
27
49,8
10
200
180
202,2
30
60,7
7,5
250
180
246,5
40,5
74
8,5
325
250
300,5
45
90,2
20
375
250
361,2
32,4
108,4
7,5
450
250
448
45
134
22
550
350
546
36
163,9 (*)
10
650
350
618
37,5
185,4 (*)
10
750
350
700
39
210 (*)
7,5
850
350
818,5
88,8
327,4
13
950
350
924,5
133,1
369,8
19
(*) Minimum Power adjustable up to 30% of gas power, to be adjusted in factory (at the commissioning) in function of installation factors, may be great value.
Содержание ADISA ADI CD 105
Страница 1: ...TECHNICAL MANUAL OF INSTALLATION USE AND MAINTENANCE 4 2020 uk ADI CD CONDENSING BOILER...
Страница 7: ...ADI CD Boiler Technical Manual 7 Models ADI CD 200 and higher...
Страница 31: ...ADI CD Boiler Technical Manual 31 12 1 Electric drawing ADI CD 70 750...
Страница 32: ...ADI CD Boiler Technical Manual 32 12 2 Electric drawing ADI CD 850 950...
Страница 69: ...www adisaheating com ADISA HEATING HIPLUS AIRE ACONDICIONADO S L...