ADI CD Boiler – Technical Manual
39
b) Electric drawing: 1 Boiler and Domestic Hot Water
BOILER
CONTROL
SIEMENS AVS3 7.29 4
14.1. Basic parameters
Activation of Domestic Hot Water
Domestic Hot Water is deactivated in default parametrization.
D.H.W.
Parameter
Function
Value
Unit
1610
Nominal setpoint temperature
60
ºC
1612
Reduced setpoint temperature
55
ºC
1614
Maximum setpoint nominal temperature
65
ºC
1620
Activation
24 hour per day
1630
Charge Priority
None/Parallel
14.2. Professional installator parameters
Functions:
-
DHW release: when DHW heating is On, the release parameter can be used to determine when – within
a 24-hour period – DHW charging shall take place.
-
Priority: when both space heating and DHW heating call for heat, the DHW priority function ensures that
while DHW charging is in progress, the boiler’s capacity is used primarily for DHW heating.
-
Legionella: setting setpoint, periodically and time of the legionella fuction.