ADI CD Boiler – Technical Manual
30
12. ELECTRIC DRAWING
The electric installation must comply with the current rules. The electric power consumed by each boiler is
indicated in the table of technical characteristics.
ADI CD 70 to ADI CD 750: The electric supply must be 220/230 V, 50 Hz, single phase, ground connection.
(Remember: in case of 220/230 V, two phases, it is necessary to install an electric insulating transformer with
one of the phases of the secondary connected to ground acting as neutral).
ADI CD 850 to ADI CD 950: The electric supply must be three-phase, 380 V, 50 Hz, ground, for the motor fan.
Protect separately the three-phase motor's electric supply (L1-L2-L3) from the boiler's electric supply (Ph-N).
Legend of the electric drawing:
1
FUSE
2
ON/OFF SWITCH
3
220V-50Hz ELECTRIC SUPPLY
4
ALARM OUTPUT
5
STATUS OUTPUT
6
BOILER PUMP
7
220V-50Hz ELECTRIC SUPPLY FOR EXTENSION MODULES “CLIP IN”
8
EXTERNAL DEMAND 0…10V
9
START/STOP EXTERNAL CONTACT
10
SAFETY LIMIT THERMOSTAT
11
IGNITION TRANSFORMER
12
GAS SHUT-OFF VALVE
16
IONIZATION ELECTRODE
14
GAS PRESSURE SWITCH
15
PROGRAMMABLE SENSOR INPUT
16
DHW TEMPERATURE SENSOR
17
OUTSIDE TEMPERATURE SENSOR
18
CASCADED SYSTEM COMMUNICATION BUS
19
MINIMUM WATER PRESSURE SWITCH
20
RETURN TEMPERATURE SENSOR
21
FLOW TEMPERATURE SENSOR
23
DISPLAY
24
EXTENSION MODULES COMMUNICATION BUS
25
PWM MOTOR SIGNAL
26
CONTACTOR
27
MOTOR FAN
Содержание ADISA ADI CD 105
Страница 1: ...TECHNICAL MANUAL OF INSTALLATION USE AND MAINTENANCE 4 2020 uk ADI CD CONDENSING BOILER...
Страница 7: ...ADI CD Boiler Technical Manual 7 Models ADI CD 200 and higher...
Страница 31: ...ADI CD Boiler Technical Manual 31 12 1 Electric drawing ADI CD 70 750...
Страница 32: ...ADI CD Boiler Technical Manual 32 12 2 Electric drawing ADI CD 850 950...
Страница 69: ...www adisaheating com ADISA HEATING HIPLUS AIRE ACONDICIONADO S L...