Parameter Settings for Keypad Entry
Appendix B
B–6
Fine Tuning Functions
“B” Group Parameters
Default Setting
User
Setting
Func.
Code
Name
-FE
(Europe)
-FU
(USA)
–FR
(Japan)
B_01
Selection of automatic restart
mode
00
00
00
B_02
Allowable under-voltage power
failure time
1.0
1.0
1.0
B_03
Retry wait time before motor
restart
1.0
1.0
1.0
B_12
Level of electronic thermal
setting
Rated
current for
each
inverter
Rated
current for
each
inverter
Rated
current for
each
inverter
B_13
Electronic thermal characteristic
01
01
00
B_21
Overload restriction operation
mode
01
01
01
B_22
Overload restriction setting
Rated
current x
1.25
Rated
current x
1.25
Rated
current x
1.25
B_23
Deceleration rate at overload
restriction
1.0
1.0
1.0
B_31
Software lock mode selection
01
01
01
B_32
Reactive current setting
Rated
current x
0.58
Rated
current x
0.58
Rated
current x
0.58
B_81
[FM] terminal analog meter
adjustment
80
80
80
B_82
Start frequency adjustment
0.5
0.5
0.5
B_83
Carrier frequency setting
5.0
5.0
12.0
B_84
Initialization mode (parameters
or trip history)
00
00
00
B_85
Country code for initialization
01
02
00
B_86
Frequency scaling conversion
factor
1.0
1.0
1.0
B_87
STOP key enable
00
00
00
B_88
Restart mode after FRS
00
00
00
B_89
Data select for digital op. OPE-J
01
01
01
Содержание L100 Series
Страница 145: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 168: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 176: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 B ...
Страница 183: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 C ...
Страница 186: ...CE EMC Installation Guidelines Appendix C C 4 L1 L2 L3 PE M 3 L100 inverter with footprint type filter ...
Страница 187: ...L100 Inverter Appendix C C 5 L1 L2 L3 PE L100 inverter with book type filter M 3 ...