NOTE:
When DC braking is performed, the inverter automatically holds the carrier
frequency at 1 kHz.
NOTE:
The carrier frequency setting must stay within specified limits for inverter-motor
applications that must comply with particular regulatory agencies. For example, a
European CE-approved application requires the inverter carrier to be less than 5 kHz.
B_84, B_85: Initialization codes –
These functions allow you to restore the factory
default settings. Please refer to
“Restoring Factory Default Settings” on page 6–8
.
B_86: Frequency display scaling –
You can convert the output frequency monitor on
D_01 to a scaled number (engineering units) monitored at function D_07. For example,
the motor may run a conveyor that is monitored in feet per minute. Use this formula:
Scaled output frequency (D_07)
Output frequency (D_01) Factor (B_86)
×
=
“B” Function
Run
Mode
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
Units
B_32 Reactive current setting
Calibrate detection of motor’s
no load (reactive) current to
improve D_02 display
accuracy, range is 0 to 32
Amperes
✔
58% rated current
A
IO 0.00A
B_81 [FM] terminal analog
meter adjustment
Adjust 8-bit gain to analog
meter connected to terminal
[FM], range is 0 to 255
✔
80
80
80
—
ADJ 080
B_82 Start frequency adjust-
ment
Sets the starting frequency for
the inverter output, range is 0.5
to 9.9 Hz
✘
0.5
0.5
0.5
Hz
Fmin 0.5Hz
B_83 Carrier frequency
setting
Sets the PWM carrier (internal
switching frequency), range is
0.5 to 16.0 kHz
✘
5.0
5.0
12.0
kHz
CARRIER 05.0kHz
B_84 Initialization mode
(parameters or trip
history)
Select the type of initialization
to occur, two option codes:
00 ...Trip history clear
01 ...Parameter initialization
✘
00
00
00
—
INIT MODE TRP
B_85 Country code for initial-
ization
Select default parameter values
for country on initialization,
four options, option codes:
00 ...Japan version
01 ...Europe version
02 ...US version
03 ...reserved (do not set)
✘
01
02
00
—
INIT SEL USA
Содержание L100 Series
Страница 145: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 168: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 176: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 B ...
Страница 183: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 C ...
Страница 186: ...CE EMC Installation Guidelines Appendix C C 4 L1 L2 L3 PE M 3 L100 inverter with footprint type filter ...
Страница 187: ...L100 Inverter Appendix C C 5 L1 L2 L3 PE L100 inverter with book type filter M 3 ...