L100 Inverter
Conf
igur
ing
Dr
iv
e P
a
ra
m
e
ters
3–35
Note 1:
When using the Multi-speed Select settings CF1 to CF4, do not display
parameter F_01 or change the value of F_01 while the inverter is in Run Mode
(motor running). If it is necessary to check the value of F_01 during Run
Mode, please monitor D_01 instead of F_01.
15
SFT
Software Lock
ON
The keypad and remote programming devices
are prevented from changing parameters
OFF
The parameters may be edited and stored
16
AT
Analog Input
Voltage/current
Select
ON
Terminal [OI] is enabled for current input (uses
terminal L for power supply return)
OFF
Terminal [O] is enabled for voltage input (uses
terminal [L] for power supply return)
18
RS
Reset Inverter
ON
The trip condition is reset, the motor output is
turned OFF, and powerup reset is asserted
OFF
Normal power-ON operation
19
PTC
PTC Thermistor
Thermal Protection
ANLG
When a thermistor is connected to terminals [5]
and [L], the inverter checks for over-
temperature and will cause trip event and turn
OFF output to motor
OPEN
A disconnect of the thermistor causes a trip
event, and the inverter turns OFF the motor
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
Содержание L100 Series
Страница 145: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 168: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 176: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 B ...
Страница 183: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 C ...
Страница 186: ...CE EMC Installation Guidelines Appendix C C 4 L1 L2 L3 PE M 3 L100 inverter with footprint type filter ...
Страница 187: ...L100 Inverter Appendix C C 5 L1 L2 L3 PE L100 inverter with book type filter M 3 ...