9.3 ADDITIONAL REFRIGERANT CHARGE CALCULATION
Although refrigerant has been charged into this unit in advance, additional refrigerant charge is required according to piping length.
Determine the additional refrigerant quantity according to the following procedure, and charge the system with it.
Record the additional refrigerant quantity to facilitate maintenance and servicing activities thereafter.
Calculating method of additional refrigerant charge (W kg)
No. Symbol
Contents
Additional
charge (kg)
1
W1
Additional refrigerant charge calculation for liquid piping (W1 kg)
Pipe diameter (mm) Total piping length (m)
Refrigerant amount for 1m pipe
(kg/m)
Additional charge
(kg)
∅
22.2
m
× 0.36 =
∅
19.05
m
× 0.26 =
∅
15.88
m
× 0.17 =
∅
12.7
m
× 0.11 =
∅
9.52
m
× 0.056 =
∅
6.35
m
× 0.024 =
Total additional charge for liquid piping =
N O T E
In the case that the quantity calculated above is less than the minimum quantity indicated in the table below, adopt
the quantity in the table below as the additional refrigerant quantity for piping liquid, regardless of the piping length.
HP
5
6
8
10
12
14
16
Minimum additional charge of base unit (kg)
2.0
2.0
2.0
2.0
3.0
3.0
3.0
For combination of the units, adopt the total minimum quantity of each base unit as the minimum additional refriger
-
ant quantity.
kg
2
W2
Additional refrigerant charge quantity for indoor unit (only for heat pump system) (W2 kg)
The additional refrigerant charge is required depending on the number of connected indoor units. Select the refriger
-
ant quantity from the following table.
Additional refrigerant charge quantity (kg)
System
Heat Pump
Heat Recovery
Model
RCI-2.0FSN3
RCI-2.5FSN3
RCI-3.0-6.0FSN3
RCI-2.0-6.0FSN3
Connectable
number
1
0.0
0.0
0.5
0.0
2
0.5
0.5
1.0
0.0
3
0.5
1.0
1.5
0.0
4 or more
1.0
1.5
2.0
0.0
kg
3
W3
Additional refrigerant charge calculation for indoor unit (W3 kg)
Additional refrigerant charge is 1kg/unit of 8HP and 10HP indoor unit.
Additional refrigerant charge of less than 8HP indoor units is not needed.
8 and 10HP Total Indoor Unit Numbers Additional Charge
× 1.0kg/unit =
kg
4
W4
The ratio of indoor unit connection capacity (indoor unit total capacity/outdoor unit capacity) additional charge
(W4 kg).
Determine the ratio of indoor unit connection capacity.
Condition
Refrigerant amount
•
I.U. Capacity Ratio is less than 100%:
0.0kg
•
I.U. Capacity Ratio is more than 100%:
0.5kg
kg
5
W
Calculation of additional charge (W kg) = W1 + W2 + W3 +W4
kg
51
PMML0294A rev.2 - 07/2014
Additional refrigerant charge
ENGLISH
PMML0294A_rev.2_02-2014.indb 51
14/07/2014 12:28:31
Содержание FSXN1E Series
Страница 2: ...PMML0294A_rev 2_02 2014 indb 2 14 07 2014 12 27 46 ...
Страница 8: ...PMML0294A_rev 2_02 2014 indb 8 14 07 2014 12 27 48 ...
Страница 14: ...PMML0294A_rev 2_02 2014 indb 14 14 07 2014 12 27 58 ...
Страница 755: ...PMML0294A_rev 2_02 2014 indb 741 14 07 2014 12 34 59 ...
Страница 756: ...Printed in Spain 00000 PMML0294A_rev 2_02 2014 indb 742 14 07 2014 12 34 59 ...