For heat recovery systems (3 pipes)
Part
Make
Permitted pipe length
(13)
≤ Recommended number
of connected indoor units
≥ Recommended number
of connected indoor units
Total pipe length
Current total liquid
pipe length
≤ 1000 m
(14)
≤ 300 m
Maximum pipe length
Current length
L1
≤ 165 m
≤ 165 m
Equivalent length
≤ 190 m
≤ 190 m
Maximum pipe length between the multikit of the first branch
and each indoor unit
L2
≤ 90 m
≤ 40 m
Maximum pipe length between each multikit and each indoor
unit
L3
≤ 40 m
≤ 30 m
Total pipe length between the CH unit and each indoor unit
*
L4
*
a+b+c+d+e
CH-6.0N(1/2): ≤ 30 m
CH-6.0N(1/2): ≤ 30 m
CH-10.0N(1/2): ≤ 10 m
CH-10.0N(1/2): ≤ 10 m
Pipe length between connection kit 1 and each outdoor unit
L5
≤ 10 m
≤ 10 m
Difference in height between
outdoor and indoor units
Highest outdoor unit
H1
≤ 50 m
≤ 50 m
Lowest outdoor unit
≤ 40 m
≤ 40 m
Difference in height between indoor units
H2
≤ 15 m
≤ 15 m
Difference in height between indoor units using the same CH
unit
H3
≤ 4 m
≤ 4 m
Difference in height between CH units
H4
≤ 15 m
≤ 15 m
Difference in height between outdoor units
H5
≤ 0.1 m
≤ 0.1 m
N O T E
For heat pump systems (2 pipes)
•
(1)
The connection kit is taken into account from the side of the
indoor unit (as connection kit 1).
•
(2)
When the maximum equivalent refrigerant pipe length (L1)
from the outdoor unit/connection kit 1 to the indoor unit is
greater than 100 m, the diameter of the gas/liquid pipe from
the outdoor unit/connection kit 1 to the first branch must be
increased using the reducer (field-supplied).
•
(3)
Where the refrigerant pipe length is greater than 100 m,
the pipe diameter does not have to be increased after the first
branch. Where the size of the multikit is greater than that of the
first branch, adjust the size of the multikit to the first branch.
Where the diameter of the pipe selected after the first branch
is greater than the diameter of the pipe after it, use the same
diameter as the inlet pipe.
•
(4)
The pipe diameter -4- must be the same as that of the indoor
unit connection.
•
(5)
Where the liquid pipe length is greater than 15 m, use
9.53 mm diameter pipe and a reducer (field-supplied).
•
(6)
Keep a direct distance of 500 mm or greater after the con
-
nection kit.
•
(7)
The installation conditions for the refrigerant pipes are differ-
ent depending on the number of indoor units connected.
•
(8)
The total pipe length permitted must be less than 1000 m
due to the maximum additional refrigerant charge limitation.
HP
5 - 10 12 14 and 16 18 - 24 26 - 54
Maximum additional
refrigerant charge (kg)
28
36
40
51
63
•
(9)
Longer piping up to 90 m is available only for base units of
FSXNH(E) / FSXN1E series. (Dip switch setting required). In
the case of base units of FSXN1E series: only for the maxi
-
mum number of connectable indoor units: (RAS-8FSXN1E ≤
14), (RAS-10FSXN1E ≤ 18), (RAS-12FSXN1E ≤ 21), (RAS-
14FSXN1E ≤ 26), (RAS-16FSXN1E ≤ 29).
For heat recovery systems (3 pipes)
•
(1)
The connection kit is taken into account from the side of the
indoor unit (as connection kit 1).
•
(2)
When the maximum equivalent refrigerant pipe length (L1)
from the outdoor unit/connection kit 1 to the indoor unit is
greater than 100 m, the diameter of the liquid pipe from the
outdoor unit/connection kit 1 to the first branch must be in
-
creased using the reducer (field-supplied).
•
(3)
Where the refrigerant pipe length is greater than 100 m,
the pipe diameter does not have to be increased after the first
branch. Where the size of the multikit is greater than that of the
first branch, adjust the size of the multikit to the first branch.
Where the diameter of the pipe selected after the first branch
is greater than the diameter of the pipe after it, use the same
diameter as the inlet pipe.
•
(4)
The pipe diameter -6- must be the same as that of the indoor
unit connection.
•
(5)
Where the liquid pipe length is greater than 15 m, use
9.53 mm diameter pipe and a reducer (field-supplied).
•
(6)
Keep a straight distance of 500 mm or greater after the con
-
nection kit.
•
(7)
In the case of branches, where the pipe length between the
three-pipe branch -F- and the furthest indoor unit exceeds
5 m, use a T-branch pipe for the three-branch liquid pipe (cor
-
responding to the same diameter, as per JIS B8607).
IU
IU
OU
OU
IU
IU
•
(8)
Where the number of connectable indoor units is greater
than four, the high/low-pressure gas, gas and liquid pipes, -4-,
-5- and -6-, must be increased by one measurement, respec
-
tively.
47
PMML0294A rev.2 - 07/2014
Piping work and refrigerant charge
ENGLISH
PMML0294A_rev.2_02-2014.indb 47
14/07/2014 12:28:29
Содержание FSXN1E Series
Страница 2: ...PMML0294A_rev 2_02 2014 indb 2 14 07 2014 12 27 46 ...
Страница 8: ...PMML0294A_rev 2_02 2014 indb 8 14 07 2014 12 27 48 ...
Страница 14: ...PMML0294A_rev 2_02 2014 indb 14 14 07 2014 12 27 58 ...
Страница 755: ...PMML0294A_rev 2_02 2014 indb 741 14 07 2014 12 34 59 ...
Страница 756: ...Printed in Spain 00000 PMML0294A_rev 2_02 2014 indb 742 14 07 2014 12 34 59 ...