![Hioki 3197 Скачать руководство пользователя страница 158](http://html.mh-extra.com/html/hioki/3197/3197_instruction-manual_2137178158.webp)
8.3 Event Specifications
150
8.3
Event Specifications
Event Type
Voltage Swell, Volt-
age Dip, Interruption
Measurement
method
Detection using voltage (½) measured every half cycle
Detected event
types
Voltage Swell: Maximum voltage (worst value),
occurrence time, recovery time, period
Voltage Dip: Residual voltage (worst value), occurrence
time, recovery time, period)
Interruption: Residual voltage voltage, detection date/
time, recovery date/time, period
Threshold
Swell: 100 to 150% of nominal voltage
Dip, Interruption: 0 to 100% of nominal voltage
Hysteresis
2% of nominal voltage
Recording
contents
Event data, event waveform, event voltage fluctuation
graph
Event data format Event number, date, time, event type, channel, status
(EVENT IN (Onset) / EVENT OUT (Recovery), period,
worst value
Inrush Current
Measurement
method
Detection using current (1/2) every half cycle
Detected event
types
Maximum current (worst value), detection time
Threshold
0 A to 5000 A (independent of current range and CT
ratio)
Recording
contents
Event data, event waveform, inrush current graph
Event data format Event number, date, time, event type
Transient
Overvoltage
Measurement
method
Comparator
Detection criteria Displays whether a positive or negative transient exists
during every voltage cycle on any of three channels
Transient detec-
tion range
50 Vrms (±70.7 Vpeak equiv.) or more, 10 to 100 kHz
Recording
contents
Event Data, Event waveform
Event data format Event number, date, time, event type, status (EVENT IN
(Onset) / EVENT OUT (Recovery), continuation period
Содержание 3197
Страница 1: ...3197 POWER QUALITY ANALYZER May 2012 Revised edition 7 3197A981 07 12 05H Instruction Manual ...
Страница 2: ......
Страница 8: ...Contents vi ...
Страница 30: ...1 3 Measurement Flowchart 22 ...
Страница 44: ...2 5 Internal Operating Status and Memory Usage 36 ...
Страница 86: ...4 6 Initializing the Instrument System Reset 78 ...
Страница 117: ...6 3 Viewing Anomalous Phenomena EVENT screen 109 6 Viewing the INRUSH Screen DETAILS WAVEFORM INRUSH ...
Страница 134: ...6 4 Viewing Recorded Data REVIEW State 126 ...
Страница 139: ...7 2 Installing JRE 131 7 5 When the installation process has completed successfully click Finish Click ...
Страница 176: ...9 4 Disposing of the Instrument 168 ...
Страница 199: ......
Страница 200: ...3197 POWER QUALITY ANALYZER May 2012 Revised edition 7 3197A981 07 12 05H Instruction Manual ...