Diagnosis
68/95
S-0-0390.0.0 (Diagnostic Number)
Figure 31: Diagnostic Number for Warning
Bit
Element
Value
Meaning
31 ... 30
Interpretation of bits 29 ... 0
0x00
Bits 29...16 (Source Type and
Diagnosis Class) are defined by
Sercos.
Bits 15...0 (Status Code) are
defined by manufacturer.
29 ... 24
Source Type
0x01
FSP IO (further details available in
IO Diagnostic message)
23 ... 20
Reserved
-
-
19 ... 16
Diagnosis Class
0x0E
Warning (C2D)
15 ... 0
Status Code
0x001C
SWD-specific Diagnosis Code of
the concerned SWD device:
„No sensor connected to connector
X2“
(see manual of concerned SWD
device)
Table 26: Coding of Diagnostic Number for Warning
S-0-0095.0.0 (Diagnostic Message)
Figure 32: Diagnostic Message for Warning
SmartWire-DT Gateway | EU5C-SWD-SERCOS
DOC160805UM01EN | Revision 1 | English | 2017-02 | Released | Public